FCU 500, FCU 505 · Edition 02.17
118
Parameters
12 .9 Password
Parameter 77
The password is designed to protect the parameter
settings.To prevent changes to parameter settings, a
password is stored in parameter 77 (0000 to 9999).
Changes to parameter settings can only be made once
this number has been entered. The password can be
changed using BCSoft. Note the effect of parameter
settings on the safe functioning of your system.
12 .10 Fieldbus communication
Parameter 80
Fieldbus communication can be activated using pa-
rameter 80 when bus module BCM 500 is connected.
A device name/network name must be entered in the
automation system for the unique identification of the
control unit (BCU/FCU) in the fieldbus system.
Parameter 80 = 0: OFF. Parameterization access using
BCSoft via Ethernet is still possible.
Parameter 80 = 1: with address check. The device
name/network name on delivery is “not-assigned-fcu-
500-xxx”. The expression “not-assigned-” must be de-
leted or may be replaced with an individual name. The
sequence xxx must be identical to the address set on
the BCM 500 using the code switches (xxx = address in
the range 001 to FEF).
Parameter 80 = 2: no address check. The device name/
network name can be selected as specified by the auto-
mation system.