FCU 500, FCU 505 · Edition 02.17
140
Technical data
18 .2 Mechanical data
Weight: 0.7 kg
Connections
– Screw terminals:
nominal cross-section 2.5 mm
2
,
wire cross-section rigid: min. 0.2 mm
2
, max. 2.5 mm
2
,
AWG: min. 24, max. 12.
Contact rating: 12 A.
– Spring force terminals:
nominal cross-section 2 × 1.5 mm
2
,
wire cross-section: min. 0.2 mm
2
, max. 1.5 mm
2
,
AWG: min. 24, max. 16,
Contact rating: 10 A (for UL 8 A).
18 .3 Environment
Ambient temperature: -20 to +60°C (-4 to +140°F),
no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).
18 .4 FCU . .H1
Terminals 5, 6, 7 and 8: Maximum voltage: ± 5 V,
input voltage range for double thermocouples:
Type K: 0 to 54.9 mV,
Type N: 0 to 47.5 mV,
Type S: 0 to 18.7 mV.
Function of Type 2 to EN 14597,
type of action: 2B, 2K and 2P,
with STL also 2A and 2N.
ESD protection of terminals 5 to 8:
Level 4 to IEC 61000-4.2 (ESD).
Maximum deviation of temperature values of STM/STL
module when using Class 1 thermocouples:
Type K: 0.63% at 25°C, ± 340 ppm/K at ambient tem-
perature,
Type N: 0.55% at 25°C, ± 340 ppm/K at ambient tem-
perature,
Type S: 1.38% at 25°C, ± 1570 ppm/K at ambient tem-
perature.
18 .5 Dimensions
100
mm
110 mm
102 mm