FCU 500, FCU 505 · Edition 02.17
23
Temperature monitoring
4 Temperature monitoring
The FCU..H1 is fitted with an integrated temperature
module.
This module can be used as a safety temperature moni-
tor (STM) to monitor the spontaneous ignition temper-
ature of the gas/air mixture or as a safety temperature
limiter (STL) to monitor the maximum furnace/flue gas
temperature. Double thermocouples are connected to
the temperature module to measure the temperature.
The functions STM and STL can also be combined. In
this case, the connected double thermocouple must re-
liably detect whether the spontaneous ignition temper-
ature (> 750°C) has been exceeded and also whether
the maximum permitted furnace temperature has been
exceeded.
The safety temperature monitor and safety temperature
limiter functions can be adjusted to the requirements of
the system using parameters 20, 22, 23, 24 and 25, see
page 82 (High temperature operation).