6.5.5 Installation of the grounding cable
Picture 9: Installation of the grounding cable
A
Heat pump flange
E M12x40 screw
B
Housing
F Seal
C
Heat buffer tank flange
G Grounding cable
D
Toothed washer
Grounding of the DHW must be performed via the grounding screw as shown on Picture 9.
The needed components are pre-assembled and included.
The grounding is performed by the following procedure:
1. The grounding of the DHW is performed by Picture 9.
2. Check the protective wire.
3. The protective wire is checked with the resistance gauge. The resistance between the
grounding connection and the inside of the casing must be between 600 and 700
Ω
.
This ensures the installation was performed correctly. If the given value is not achieved,
check whether the grounding cable is installed correctly.
7
Commissioning of the device
7.1 Filling the device with water
After an expert has connected the HP to the water supply, the system has to be filled with
water and thoroughly vented. This is performed by opening all taps in the residence. When
water flows uninterruptedly from all taps, the system is thoroughly vented.
CAUTION
The heat pump must never operate without water in the buffer tank for DHW.
Otherwise, damage to the device may occur.