OPERATING INSTRUCTIONS
efuturo Wallbox
1. Mark the mounting holes using the supplied drilling template and a spirit level.
2. Drill the holes in the wall with the diameter provided for the selected mounting material.
3. Route the feeder cable to the position indicated on the drilling template.
4. For the electrical connection, approx. 20 cm of cable are required inside the charging station.
5. Open the charging station – see „Opening the charging station“.
6. Insert the feeder cable into the charging station through the cable entry points.
7. Screw the charging station to the wall using suitable mounting materials. Check again with the spirit level and if
necessary finely adjust the Wallbox with the screws.
8. Check the charging station for firm and secure fastening.
Electrical connection
Danger
Fatal shock hazard!
Components are live. Touching live parts will result in electric shock, burns or death. Observe the following points
before working on the electrical system.
• Disconnect the device from the power supply
• Secure against switching back on
• Check freedom from voltage
• Grounding and short circuiting
• Cover adjacent live parts and secure the danger zone
!
During installation, also observe the following points:
• This device is only allowed to be installed, started up and serviced by qualified electricians in compliance with the
applicable national regulations, see the „Qualification of personnel“ chapter
• Before connecting the device, ensure that it is not live, or take suitable protective measures
Observe the following points when connecting to the power supply:
• For installation in Germany, observe DIN VDE 0100 part 530
• When installing in other countries, observe the applicable national/local regulations
• For three-phase current connection, make sure there is a clockwise rotating field
Security and personal protection
Danger
Fatal shock hazard!
• All current sensitive residual current circuit breakers (type B) must not be mounted behind pulse current sensitive
residual current circuit breakers (type A).
!
The charging stations are equipped with a
type B
residual current circuit breaker regardless of the equipment variant.
Observe the following points when connecting the charging station:
• Each charging station must be connected via a separate circuit breaker.
• No other circuits are allowed to be connected to this circuit breaker
Design of the on-site circuit breaker
The rating of the on-site circuit breaker is selected by a suitable qualified electrician.