5 Installation at Site
18 of 44
Hya-Duo D FL
5 Installation at Site
5.1 Checks to be carried out prior to installation
WARNING
Installation on mounting surfaces which are unsecured and cannot support the
load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class X0 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.
NOTE
The anti-vibration mounts provide adequate insulation against solid-borne noise.
NOTE
Do not operate the fire-fighting system near living quarters and/or sleeping
quarters.
NOTE
Observe the installation requirements to DIN 14462.
Before beginning with the installation check the following:
▪
All structural work required has been checked and prepared in accordance with
the dimensions in the outline drawing.
▪
The fire-fighting system can be operated on the power supply network according
to the data on the name plate. (
▪
The place of installation is frost-free.
▪
The place of installation can be locked.
▪
The place of installation is well-ventilated.
▪
A suitably dimensioned drain connection (e.g. leading to a sewer) is available.
▪
If the system is installed below the flood level, the country-specific drainage
regulations must be complied with.
▪
If expansion joints are used, take note of its creep resistance. Expansion joints
must be easily replaceable.