21
(mm
2
)
(mm
2
)
(mm
2
)
(mm
2
)
(mm
2
)
80
50
50
50
95
25
100
70
50
50
120
35
120
95
70
70
150
50
150
120
95
95
185
70
◆
When selecting, connecting, and routing power cables, follow local safety regulations and
rules.
◆
If external conditions such as cable layout or ambient temperatures change, perform
verification in accordance with the IEC-60364-5-52 or local regulations.
◆
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
◆
If primary loads are non-linear loads, increase the cross-sectional areas of neutral
wires1.5–1.7 times.
◆
The nominal battery discharge current refers to the current of forty 12 V batteries at 480V
in standard configuration.
◆
The maximum battery discharge current refers to the current when forty 12 V batteries in
standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop
discharging.
◆
The battery cable specifications are selected based on 40 batteries by default and
compatible with application scenarios with 30–50 batteries.
◆
When the mains input and bypass input share a power source, configure both types of input
power cables as mains input power cables. The cables listed in Table are used only when
the following requirements are met:
− Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E).
− The ambient temperature is 30°C.
− The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
− 90°C copper flexible cable.
− The length of the AC power cables of a UPS is no longer than 30 m and DC power cables
no longer than 50 m.
3.7.2
Power cable connector requirements
Model
Connector
Connection
Mode
Bolt Type
Bolt Hole
Diameter
Torque
80k
Mains input
connector
Crimped OT
terminals
M10
11mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
11mm
26N•m
Battery input
connector
Crimped OT
terminals
M10
11mm
26N•m
Output
connector
Crimped OT
terminals
M10
11mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
11mm
26N•m
100k
Mains input
connector
Crimped OT
terminals
M10
11mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
11mm
26N•m
Summary of Contents for HPM3300E
Page 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Page 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Page 43: ...42 ...
Page 48: ...47 ...
Page 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...