22
Battery input
connector
Crimped OT
terminals
M10
11mm
26N•m
Output
connector
Crimped OT
terminals
M10
11mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
11mm
26N•m
120k
Mains input
connector
Crimped OT
terminals
M10
11mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
11mm
26N•m
Battery input
connector
Crimped OT
terminals
M10
11mm
26N•m
Output
connector
Crimped OT
terminals
M10
11mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
11mm
26N•m
150k
Mains input
connector
Crimped OT
terminals
M10
11mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
11mm
26N•m
Battery input
connector
Crimped OT
terminals
M10
11mm
26N•m
Output
connector
Crimped OT
terminals
M10
11mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
11mm
26N•m
3.7.3
Recommended input front-end and output back-end circuit breakers
UPS capacity
Component
Specifications
80k
Mains input breaker
160A
3P
Bypass input breaker
160A
3P
Output breaker
160A
3P
Battery breaker
250A
3P
100k
Mains input breaker
200A
3P
Bypass input breaker
200A
3P
Output breaker
200A
3P
Battery breaker
320A
3P
120k
Mains input breaker
250A
3P
Bypass input breaker
250A
3P
Output breaker
250A
3P
Battery breaker
400A
3P
150k
Mains input breaker
320A
3P
Bypass input breaker
320A
3P
Summary of Contents for HPM3300E
Page 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Page 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Page 43: ...42 ...
Page 48: ...47 ...
Page 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...