27
Note
:
The BAT+ of the UPS connect poles is connected to the anode of the positive
battery, the BAT-N is connected to the cathode of the positive battery and the anode
of the negative battery, the BAT- is connected to the cathode of the negative battery.
Factory setting of the long-run unit is battery quantity---36pcs, battery
capacity---12V100AH (charger current 15A). When connecting
30/32/34/38/40/42/44/46/48/50 batteries, please re-set desired battery quantity and
its capacity after UPS starts at AC mode. Charger current could be adjusted
automatically according to battery capacity selected. All related settings can be done
through LCD panel or monitoring software
CAUTION!
Ensure correct polarity battery string series connection. i.e. inter-tier
and inter block connections are from (+) to (-) terminals.
Don’t mix batteries with different capacity or different brands, or
even mix up new and old batteries, either.
WARNING!
Ensure correct polarity of string end connections to the Battery
Circuit Breaker and from the Battery Circuit Breaker to the UPS
terminals i.e. (+) to (+) / (-) to (-) but disconnect one or more battery cell
links in each tier. Do not reconnect these links and do not close the
battery circuit breaker unless authorized by the commissioning
engineer.
3.10 Online UPS Modules Replacement
For the UPS, modules must be inserted to make a complete UPS system.
The replacement of UPS module is very simple and can be operated online. The control
system of the UPS can detect the inserted or removed module(s) automatically. The user
may operate easily by following the steps mentioned below.
◆
NOTE: The UPS module is rather heavy, please move it by two people!
Summary of Contents for HPM3300E
Page 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Page 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Page 43: ...42 ...
Page 48: ...47 ...
Page 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...