CAUTION!
Read this information to avoid equipment damage
2
.
Main Features
2.1 Summarization
Our UPS is a kind of three-in- three -out high frequency online UPS, it provides three
specifications: The 30~150kVA. The products are modularized and adopt the N+X redundancy. It
can flexibly increase the number of the UPS modules according to the load capacity which is
convenient for flexible allocation and gradually investment.
The UPS can solve most of the power supply problems, such as blackout, over-voltage,
under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage
fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency
fluctuation, etc..
This UPS can be applied to different applications from computer device, automatic
equipment, communication system to industry equipment.
2.2 Functions and Features
◆
Rack modular design
Modular design, compatible with 19” standard rack cabinet, convenient to be integrated with
servers.
◆
Integrated solution for data center
◆
Digital control
◆
Modularized design
◆
High power-density design
◆
The height of the single module is 3U.
◆
N+X parallel redundancy
This series UPS adopts N+X parallel redundancy design, user can set different redundancy
according to the importance of the load. While the redundancy modules are set more than
two, the availability of UPS system will achieve 99.999%, which may satisfy the required
reliability of the critical load connected. Through LCD display setting, you may configure the
required quantity of the redundancy unit. When the load connected is over the number of the
redundancy, the UPS will alert right away. The design of the MTBF (Meantime before Failure)
is up to 250,000 hours.
This series can set the number of redundancy modules. When the load exceeds the
redundancy setting, the UPS can still work normally and simultaneously send out
corresponding warning as long as the load doesn’t exceed the total capacity of modules.
◆
Parallel redundant control system
◆
Optimizing distributed convergence for the cabinet
◆
Centralized bypass
◆
Common Battery
◆
Automatic charge current adjustment according to battery capacity connected.
◆
3-Stage
Intelligent charging
Summary of Contents for HPM3300E
Page 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Page 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Page 43: ...42 ...
Page 48: ...47 ...
Page 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...