37
Appendix 1 Specifications
Model
10k (S/H)
15k (S/H)
20k (S/H)
Capacity
10kVA
15kVA
20kVA
10kW
15kW
20kW
Input
Phase
380/400/415Vac,(3Ph+N+PE)
220/230/240Vac,(L+N+PE)
Rated Voltage
380/400/415Vac
220/230/240Vac
Voltage Range
208~478Vac
120~276Vac
Frequency Range
40-70Hz
Power Factor
≥
0.99
Current THDi
≤
3%(100% non linear load)
Bypass Voltage Range
Max. voltage: 220Vac: +25%(op10%,+15%,+20% )
230Vac: +20%(op10%,+15% )
240Vac: +15%(op10% )
Min. voltage: -45% (optional -10%, -20%, -30%)
Frequency protection range: ±10%
Generator Input
Support
Output
Phase
220/230/240Vac,(L+N+PE)
Rated Voltage
220/230/240Vac
Power Factor
1.0
Voltage Regulation
±1%
Frequency
Utility Mode
±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency(optional)
Battery Mode
(50/60±0.1%)Hz
Crest Factor
3:1
Power factor
1.0
THD
≤
2% with linear load
≤
5% with non linear load
Efficiency
Up to 94.5%
Battery
Voltage
Standard
unit
±120Vdc(20pcs9AH)
(20pcs7AH;2x20pcs
7/9AH optional)
±120Vdc(2x20pcs 9AH)
(2x20pcs 7AH optional)
Long run
unit
±96/108/120Vdc (16~20 pcs, 16 pcs define, Standard unit
and 20 pcs no power derating; 18 pcs output power factor
0.9; 16 pcs output power factor 0.8;)
Optional:
±192/204/216/228/240Vdc(32/34/36/38/40pcs optional)
Charge
Current(A)
Standard unit
1.35A
2.7A
Long run
unit
14A max.
16A max.
18A max.
charge current can be set according to battery capacity installed
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Overload
AC Mode
Load
≤
110%: last 60min change to bypass,
≤
125%: last
10min, change to bypass,
≤
150%: last 1min change to
bypass, >150% change to bypass immediately
Bat. Mode
Load
≤
110%: last 10min,
≤
125%: last 1min,
≤
150%: last
5S, >150% shut down UPS immediately
Bypass Mode
Breaker 64A
Breaker 100A
Breaker 126A
Short Circuit
150A peak
270A peak
300A peak
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS
immediately
Battery Low
Alarm and Switch off