21
Setting data2 Setting data3
Setting data3 Record data
Version data Module detailed record data
Setting of battery test Setting of Buzzer
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
Work Mode Single
LBS Group Setting Master
System Voltage Level 220V
System Frequency Level
50HZ
Auto Turn-on
Enable
Bypass Frequency Range
2%
Bypass Volt. Upper Limit
10%
Back
Bypass Volt. Lower Limit
-30%
O/P Volt Micro tuning
0%
Next
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
Parallel ID 01
M/S hot standby Cyc. Invalid
UPS Output
Enable
Pre-Alarm Time
14 Min
Float Volt Revise
0.001
Parallel Amount
04
Parallel Redundancy 01 Back
Next
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
Single Battery Volt. 12V
Battery Number 20
Battery Group 1
Single Battery Capa. 100AH
Boost Upper Limit Volt. 2.31
Float Base Volt. 2.25
Battery Protect Volt. 1.70
Boost Charge
Enable Back
Boost Last Time
231 Min
Max Charge Current
25A
Next
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
0001 12-21 15:00:26 On Line
0002 12-21 15:00:25 Rectifier Active..
0003 12-21 15:00:10 Int.Input Switc..
0004 12-21 15:00:08 Int.Bypass Swit..
0005 12-21 15:00:05 Int.Output Swit..
0006 12-21 15:00:00 Ext. Output Swit..
Back
Next
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
SYS Version: V02
×
10
LCD Version: 701
×
02F
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
Battery Test
Buzze
Defau
30KVA 22-12-2008
ID:01 08:30
◄
Setting
Record
Version
►
Battery Test
Buzze
Defau
ID:00 Record:0001
▲
2008-12-21 15:00:25
Status:On Line
▼
Event: On Line
Alarm:
CODE:CC00-0000 DF00-0000 0000
0000-0000 0000-0000
Quit
ONLINE
ONLINE
Command
Command
ONLINE
ONLINE
Command
Command
ONLINE
ONLINE
Command
Command
ONLINE
ONLINE
Command
Command
Battery Test
▼ 10Min ▲
Ensure Cancel
Buzzer Set
On Mute
Ensure Cancel
Summary of Contents for YDC9300-RT Series
Page 1: ......