Cabinet Paral Redunt Units:
Parallel redundancy cabinet number, can modify the
redundancy cabinet number after set work mode to
parallel mode. The value can be 0~5, default value is 0.
Output Freq:
Output frequency, The value can be 50Hz or 60Hz.
Output Volt Level:
Output voltage level, The value can be 220V, 230V, 240V.
Output Ivn Volt Regu:
Inverter voltage regulated, The value can be -5%~0~+5%, step is
0.5%, default value: 0.
Power Walk in:
this is enable the UPS to control the interval that each module transfers
from battery mode to normal mode, which reduces the impact on the
generator or power grid. The value can be 1~20, default value is 1.
Inter Power Walk in:
this is enable the UPS to control the interval that each rack
transfers from battery mode to normal mode, which reduces the
impact on the generator or power grid. The value can be 0~200,
default value is 10.