53
Battery Group:
Must modify the numer to actual configuration, The value can be 1~8,
default value is 1.
Battery number:
Must modify the numer to actual configuration, The value can be
30~50, default value is 32.
Single Battery Capability:
Must modify the value to actual configuration, The value can
be 7~2000.
Boost/Float conversion:
boost charge and float charge alternate time, The value can
be 0~20.
Chg.cur.limiting coef.:
The charging current limit is a multiple of the battery capacity.
The value can be 0.05–0.15, and is 0.1 by default.
Cell float voltage:
The float voltage value can be 2.23-2.30 V/cell, and is 2.25 V/cell by
default.
Cell boost voltage:
The battery equalized voltage value can be 2.30–2.40 V/cell, and is
2.30 V/cell by default.
Aver charging Duration:
boost charge time limit, the value can be 1–999min , and is
240 by default.