69
Module charge current
(A)
max.
20A
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down
UPS immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO
Shut down UPS immediately
Battery
Advanced Battery Management
Noise Suppression
Complies with EN62040-2
Communication Interface
CAN, RS485, FE, LBS, Parallel, Relay card, SNMP
card(optional)
Environment
Operating
Temperature
0
℃
~
40
℃
Storage Temperature
-25
℃
~
55
℃
Humidity
0
~
95% non condensing
Altitude <
1500m
Display
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Status LED
UPS Fault, Alarm and normal
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage, parameter
set, history record…
Other
Standard cabinet
Dimensions(W*D*H)
/ /
600*850*2000
Full cabinet
Dimensions(W*D*H)
(mm)
600*850*1200 600*850*1600
Module
Dimensions(W*D*H)
(mm)
440*620*130
Cabinet Weight (Kg)
180 230 200
Module Weight (Kg)
32
Safety Conformance
CE,EN/IEC 62040-3,EN/IEC 62040-1-1
Model
300kVA
400kVA
500kVA
600kVA
Cabinet capacity
(VA/W)
50k~300k /
50k~300k
50k~400k /
50k~400k
50k~500k /
50k~500k
50k~600k /
50k~600k
Module capacity
(VA/W)
50k / 50k
Max. module number
6
8
10
12
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
138~485Vac
◆
At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆
At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac