75
Appendix 7 REPO instruction
Definition of port
:
Normally open :
Normally close :
Connection between the button and UPS REPO port.
Button UPS
REPO
Description
Pin 1
Pin 1
GND
Pin 2
Pin 2
EPO
◆
In addition to the local EPO push button on the front panel of the UPS (that stops operation of that
module when pressed for more than 3 second), the UPS also supports a remote emergency stop
(REPO).
◆
A remote emergency stop switch (Dry contact signal and “normally open” - not provided) can be
installed in a remote location and connection through simple wires to the REPO connector.
◆
The remote switch can be connected to several UPS’s in a parallel architecture allowing the user to
stops all units at once.
◆
Additionally, a second system (not provided) can be connected to the remote switch to disconnect
the main input and the secondary (bypass) input sources