SKY PRO 1800 FORCED CIRCULATION MANUAL
C
C
27
2
nd
case
3
rd
case
3.13 Mounting the sensor
Place the sensor into the probe holder well of the solar collector near the flow pipe (as shown in the picture)
and fasten it so as to prevent any leaks. Furthermore, only material that is suitably resistant to high
temperatures can be used to install the probe component. The probe cable must not pass close to cables
with a voltage that exceeds 50 V. The probe provides by Kloben is a PT1000 HT for high temperatures.
For correct introduction of the F1 probe (recognisable by the grey silicone cable) follow the indications given
below:
1)
Insert the sensitive element of the probe F1 into the relative probe-holder well mounted on the panel, in
the direction
indicated in the figure above.
2)
Leave the cable to run to the bottom of the well, making sure not to block it completely.
3)
Successively, make the electric connections with the solar control unit, carefully following the instructions
attached to
the same.
4)
Connect the probe electrically to the control unit.
It is advised to wear work gloves and protective goggles in order to prevent injury if the vacuum tube
should accidentally break.