background image

    Operating instructions  KEA 202 INS         - 

12 / 22

 -     File: 

BA_KEA 202 INS_EN_Ver 2016-07-01.docx

 

 

______________________________________________________________________________________ 

Alfred Kuhse GmbH 

Telefon: +49 4171-798-0 

kuhse@kuhse.de 

Technische Änderungen vorbehalten 

An der Kleinbahn 39, D-21423 Winsen (Luhe) 

Telefax: +49 4171-798-117 

www.kuhse.de 

 

 

10.1. 

Display and acknowledgement of alarms 

If there is no new actual pending, the Actual Alarms group is selected with the [→] and [←] buttons or by 
simultaneously pressing LED

 

T

EST

 

and [←] button.  

When a new alarm occurs, the 

FAULT

♠ indicator flashes (yellow indicator in the left row of the panel). At the 

same time, the acoustic signal is switched on. The horn is switched off and the display is automatically 
switched to the page with the pending alarms using the 

 

A

LARM 

O

FF

 button. 

Either <NEW> for unacknowledged alarms or <ACKN> for acknowledged alarms comes before the text of 
the pending alarm. 
 
 
 

 

 
    

           

Unacknowledged alarm                               

  Acknowledged alarm                      Display without pending alarms  

 

The  displayed  alarm  is  acknowledged  or  if  the  fault  cause  is  remedied,  an  already  acknowledged  alarm  is 
deleted by pressing the 

 

A

LARM 

O

FF

 button. If all alarms are acknowledged, the Common Alarm indicator lights 

up permanently. It starts flashing again with a new alarm. If all alarms are deleted, the common alarm indicator 
is switched off. The pending alarms are displayed successively and can be acknowledged or deleted using the 
[↑] and [↓] buttons. 
From the next page (acce

ssible by pressing the [→] button), all pending alarms are displayed successively in 

one second intervals. Alarms can no longer be acknowledged or deleted here 
If no alarms are pending, the note -No alarms present- is displayed when opening the pages. 
 

10.2. 

Description of the alarms 

10.2.1. 

Engine does not switch off  

If the running message of the motor is still pending after the stop time expires, the Motor does not come to a 
standstill alarm is activated.

 This indicates that the stop equipment (e.g. burned stopping solenoid, jam-

ming gas solenoid valve) of the motor is defective. 

10.2.2. 

False start 

The alarm is activated if the genset has not started at the end of the start program. The automatic sys-
tem is locked for any further automatic start-up. 

10.2.3. 

Motor fault 

The alarm starts up if the motor is already running and is brought to a standstill without a stop com-
mand. The automatic system is locked at the same time. 

10.2.4. 

Overspeed 

For the overspeed monitoring, either the generator frequency or the frequency of a pick-up is used. 

If 

the generator frequency is used for detecting the overspeed, the Generator undervoltage alarm must be par-
ametrised as an alarm to be switched off in order to ensure the protection of the machine, even in the event 
of generator voltage failure

 

10.2.5. 

Alarms 13 and 14 

Both these alarms are delayed by 0 to 240 sec. by the signal transmission, i.e. for the alarm contact to 
issue an error, the signal must be pending for a parametrised time. 

Furthermore, both these alarms are 

also effective in the Off operating mode (Off), but without switching on the horn.

 This means criteria (such 

as tank overfilling, leakage warning) that must always be signalled can be monitored.  

10.2.6. 

Battery voltage monitor 

On the direct monitoring output, a relay can be parameterised (at standby current) such that the message is 
passed on with standby current even when in Off operating mode.

  

NEW    GENERATOR 
OVERLOAD 

ACKN   GENERATOR 
OVERLOAD 

NO ALARMS 
         PRESENT 

Summary of Contents for KEA 202 INS

Page 1: ...ions and fastenings as its predecessor replacement is simple Four dedicated operating messages and four programmable operating displays can be labelled by replaceable paper strips and are indicated by...

Page 2: ...missioning 4 5 3 Connections 4 5 4 Battery and supply voltage 4 5 5 Coils 4 6 Basic operation of automatic system 5 6 1 Operation of the display 5 6 2 Display contrast setting 5 6 3 Parameterisation 6...

Page 3: ...monitor 13 10 2 11 Monitoring the flows 13 10 2 12 Maintenance interval reached 13 10 2 13 Maintenance interval exceeded 13 11 Actual values 14 11 1 Description 14 12 Further functions 15 12 1 Freque...

Page 4: ...ions especially those of the VDE must be observed 2 The information in the service instructions must be complied with prior to commissioning 3 The parameterisation of the unit must be carried out in s...

Page 5: ...key and pressing the key the ACTUAL VALUES group is directly selected by holding LED TEST and pressing the key the display of alarms is directly selected To change a parameter first enter the valid I...

Page 6: ...dent and PIN numbers Parameterisation is described in the Service Manual You do not need to enter a valid Ident number to modify parameters of this group Duration of display illumination The backgroun...

Page 7: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 8: ...if the measuring voltage is connected with a left rotation field or if the volt age has too large an asymmetry of the vectors If an enabled monitoring signals a deviation from the nominal range the r...

Page 9: ...the negative potential as otherwise no start is carried out 8 2 Off operating mode The Off position is automatically selected reset function during the application of battery voltage in order to preve...

Page 10: ...after the start function is enabled If the generator voltage with its voltage and frequency values are within the nominal ranges generator operation can be switched on using the GEN ON I key resp swi...

Page 11: ...ed when the motor stops e g battery undervoltage except in the Off operat ing mode They are designated as without delay The alarm messages 13 and 14 are always monitored even in the Off operating mode...

Page 12: ...If no alarms are pending the note No alarms present is displayed when opening the pages 10 2 Description of the alarms 10 2 1 Engine does not switch off If the running message of the motor is still pe...

Page 13: ...l coupling switch can be switched off via an output to be parametrised 10 2 10 Alarms of the voltage monitor The frequency and voltage deviations of the generator can be displayed as error messages An...

Page 14: ...3 ASYMMETRIC LOAD Power load of the generator for THERMAL OVERLOAD ALARM Maximum asymmetric load of the three generator flows 7 BATTERY 26 6 V VOLTAGE Display of the battery voltage The measuring sig...

Page 15: ...are counted up to 999 hours and 59 minutes It is used for recording short runtimes e g during trial operations or mains failures It can be set to 00 00 without the main operating hours counter being c...

Page 16: ...le relays 35 V DC 1 Amp e g for acoustic transducer Standards regulations VDE 100 part 710 13 2 Analogue inputs and outputs Gnerator voltage monitor 3 phase adjustable in 1 Volt steps With incorrect r...

Page 17: ...o top hat rails dimensions depth 210 x 100 x 50 mm Weight approx 0 5 kg any installation position protection rating IP 00 equipped with 15 relays of which 14 can be parametrised contact loading max 25...

Page 18: ..._____________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen...

Page 19: ...__________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Lu...

Page 20: ...___________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Luhe Tele...

Page 21: ...______________________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 214...

Page 22: ...22 22 Operating instructions KEA 202 INS File BA_KEA 202 INS_EN_Ver 2016 07 01 docx 22 22 16 Drilling template scale 1 1 print out without scaling...

Reviews: