background image

    Operating instructions  KEA 202 INS         - 

5 / 22

 -     File: 

BA_KEA 202 INS_EN_Ver 2016-07-01.docx

 

 

______________________________________________________________________________________ 

Alfred Kuhse GmbH 

Telefon: +49 4171-798-0 

kuhse@kuhse.de 

Technische Änderungen vorbehalten 

An der Kleinbahn 39, D-21423 Winsen (Luhe) 

Telefax: +49 4171-798-117 

www.kuhse.de 

 

 

6. 

Basic operation of automatic system 

The automatic system can be operated very easily, as with all previous models and without menu navigation. 
The operating mode can be selected using four buttons. In 

MANUAL

 and 

TEST

 mode, the generator is switched 

on and off using the buttons arranged in the mimic diagram. 
In M

ANUAL

 mode, the S

TART

 button is programmed for a manual start. The LED T

EST

 and A

LARM 

O

FF

 buttons 

are self-explanatory. 
During normal operation, the display is only required to display pending alarms and the actual values. The 
menu is also easy to use here: Use the [→] and [←] keys to select the required group (alarms or actual val-
ues) and use the [↑] and [↓] keys to display the required actual value or pending alarms. 

6.1. 

Operation of the display 

You select a parameter or a value just like you read a book. The different groups are saved as 'pages'. The 
groups can be scrolled through forwards and backwards using the [→] and [←]

 

 cursor keys. Within a group, 

they are 

read like 'lines' of a text from top to bottom. The lines are selected by pressing the cursor buttons [↓] 

(down) and [↑] (up). If the ‘end of the page’ is reached, it starts again from the top or the bottom. 
By holding the LED

 

T

EST

 

key and pressing the [←] key, the A

CTUAL VALUES

 group is directly selected; by 

holding LED

 

T

EST

 

and pressing the [→] key, the display of alarms is directly selected. 

To change a parameter, first enter the valid ID number. A Group 0 parameter, -G

ENERAL 

P

ARAMETERS

-, can 

be changed without entering a valid ID number. A parameter is changed as described above. 
1. 

Select the group of the desired parameters with the [←] and [→] buttons. 

2. 

The display with the required parameter is selected using the [↑] or [↓] key. A maximum of two parameters 
are displayed. 

3.  Press the O

FF

 and LED

 

T

EST

 buttons (function P

ARA ON

 or P

ARA OFF

) at the same time. The parameteri-

sation mode is initiated and is indicated by the solid cursor [ █ ]. It is no longer possible to change the 
group. 

4.  The required parameter is 

selected with the [↑] or [↓] key.  

5.  By simultaneously pressing O

FF

 and A

LARM OFF

 (E

NTER

 function), the displayed line is defined, which is 

indicated by the cursor shape that now displays the parameter position to be changed by an underscore  [ 

_

 ]. The line may no longer deselected. 

6. 

The parameter position to be changed is selected using the [←] and [→] cursor buttons and a numeric 
parameter is increased or decreased by 1 using the [↑] and [↓] buttons. A parameter that is displayed by a 
letter (prefix, alarm coding), is changed using these buttons in reverse order. 

7.  The displayed parameter is applied by simultaneously pressing Off and Alarm off.  

 

If you want to cancel the parameterisation step, simultaneously press the Off and LED Test buttons instead 
of O

FF

 and A

LARM OFF

.

 

6.2. 

Display contrast setting 

The display contrast is increased by holding the LED T

EST

 

button and pressing the [↑] button (display becomes 

darker) or decreased by holding the [↓] button (display becomes brighter). 

 

 

 

Summary of Contents for KEA 202 INS

Page 1: ...ions and fastenings as its predecessor replacement is simple Four dedicated operating messages and four programmable operating displays can be labelled by replaceable paper strips and are indicated by...

Page 2: ...missioning 4 5 3 Connections 4 5 4 Battery and supply voltage 4 5 5 Coils 4 6 Basic operation of automatic system 5 6 1 Operation of the display 5 6 2 Display contrast setting 5 6 3 Parameterisation 6...

Page 3: ...monitor 13 10 2 11 Monitoring the flows 13 10 2 12 Maintenance interval reached 13 10 2 13 Maintenance interval exceeded 13 11 Actual values 14 11 1 Description 14 12 Further functions 15 12 1 Freque...

Page 4: ...ions especially those of the VDE must be observed 2 The information in the service instructions must be complied with prior to commissioning 3 The parameterisation of the unit must be carried out in s...

Page 5: ...key and pressing the key the ACTUAL VALUES group is directly selected by holding LED TEST and pressing the key the display of alarms is directly selected To change a parameter first enter the valid I...

Page 6: ...dent and PIN numbers Parameterisation is described in the Service Manual You do not need to enter a valid Ident number to modify parameters of this group Duration of display illumination The backgroun...

Page 7: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 8: ...if the measuring voltage is connected with a left rotation field or if the volt age has too large an asymmetry of the vectors If an enabled monitoring signals a deviation from the nominal range the r...

Page 9: ...the negative potential as otherwise no start is carried out 8 2 Off operating mode The Off position is automatically selected reset function during the application of battery voltage in order to preve...

Page 10: ...after the start function is enabled If the generator voltage with its voltage and frequency values are within the nominal ranges generator operation can be switched on using the GEN ON I key resp swi...

Page 11: ...ed when the motor stops e g battery undervoltage except in the Off operat ing mode They are designated as without delay The alarm messages 13 and 14 are always monitored even in the Off operating mode...

Page 12: ...If no alarms are pending the note No alarms present is displayed when opening the pages 10 2 Description of the alarms 10 2 1 Engine does not switch off If the running message of the motor is still pe...

Page 13: ...l coupling switch can be switched off via an output to be parametrised 10 2 10 Alarms of the voltage monitor The frequency and voltage deviations of the generator can be displayed as error messages An...

Page 14: ...3 ASYMMETRIC LOAD Power load of the generator for THERMAL OVERLOAD ALARM Maximum asymmetric load of the three generator flows 7 BATTERY 26 6 V VOLTAGE Display of the battery voltage The measuring sig...

Page 15: ...are counted up to 999 hours and 59 minutes It is used for recording short runtimes e g during trial operations or mains failures It can be set to 00 00 without the main operating hours counter being c...

Page 16: ...le relays 35 V DC 1 Amp e g for acoustic transducer Standards regulations VDE 100 part 710 13 2 Analogue inputs and outputs Gnerator voltage monitor 3 phase adjustable in 1 Volt steps With incorrect r...

Page 17: ...o top hat rails dimensions depth 210 x 100 x 50 mm Weight approx 0 5 kg any installation position protection rating IP 00 equipped with 15 relays of which 14 can be parametrised contact loading max 25...

Page 18: ..._____________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen...

Page 19: ...__________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Lu...

Page 20: ...___________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Luhe Tele...

Page 21: ...______________________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 214...

Page 22: ...22 22 Operating instructions KEA 202 INS File BA_KEA 202 INS_EN_Ver 2016 07 01 docx 22 22 16 Drilling template scale 1 1 print out without scaling...

Reviews: