12.4. 

Auto operating mode  

12.4.1. 

Peak load without mains failure control function 

Systems that are only intended for peak load operation, i.e. without mains failure control function, can be inde-
pendently operated without a central control system (ZLT). All control functions that are specified by VDE-AR-
N 4105:2021-08 are fulfilled. Mains disconnection is carried out by the generator circuit breaker. The busbar 
monitor is used to detect a return of power as the mains voltage is measured continuously here.  
The control orders (power specification and limitation) for the automatic system are either issued via the con-
nections of the relay unit or can be issued by a central control system (ZLT) over the CAN_0 bus. Systems with 
several gensets must be linked together over the CAN_0 bus. 
A remote start is only possible when all requirements of the VDE-AR-N 4105 with regard to the load enable, and 
mains voltage and frequency are fulfilled. 
In the event of a mains failure (detected by the internal busbar monitor), the generator is immediately switched 
off and a switch-off pulse is issued for the external mains switch. If several gensets are switched on, they are 
switched off simultaneously by a broadcast telegram on the CAN bus. 
If the power enable falls back to 0%, the genset is relieved and shuts down. 

12.4.2. 

Standalone operation without peak load 

The mains coupling on signal (connection 21 of the KRK-12) is permanently not issued. This deactivates the 
voltage monitor in accordance with VDE-AR-N 4105 or E VDE-AR_N 4120, as only standalone operation is 
intended. With a remote start command, the genset starts up and only switches to the bar while observing the 
locking conditions. The locked connection is made as described below. If several gensets are used, one genset 
is dynamically determined as a master and ensures the load distribution. 
A deselected, relieved genset (except for the last one) switches off and shuts down after the run-on time. 

12.4.3. 

Peak load with mains failure control function 

For mains voltage monitoring of the emergency current operation, an external voltage monitor must be used. A 
mains failure during mains parallel operation is detected by the internal voltage monitor, as the mains voltage is 
on the busbar. The external voltage monitor is required for detecting a return of power and mains failure outside 
mains parallel operation. 
The genset is always started by the remote start input. For an automatic start, any auxiliary drives are switched 
on and the parametrised start program is triggered after the start function is enabled. If the genset has not 
started at the end of the start program, the failed start alarm is issued and the automatic system inhibited. 
After the genset has started up, the generator is switched on while observing the locking conditions as soon as 
the nominal generator voltage and frequency are reached. 
After removing the start command, the genset switches the generator off, continues to run without load for the 
set run-on time and is then shut down. 

12.4.4. 

Sprinkler prompt 

The genset is started and can only be stopped by the Off or Emergency Stop key. The exact process (according 
to VDS 2100-22) is described further below. 

12.5. 

Test operating mode 

12.5.1. 

General 

Test operation is a manual operating mode in which some functions run automatically for safety reasons. If a 
remote start command occurs during test operation, the system switches to generator operation. In these cases, 
it is no longer possible to switch off the generator circuit breaker manually. 

It is then necessary to switch back to 

Auto in order for all subsequent processes to be carried out automatically in accordance with the VDE specifica-
tions, and cannot be manually overridden.

 

12.5.2. 

Generator operation 

After selecting the test position, any auxiliary drives are switched on and the parametrised start program is 
triggered after the start function is enabled. If the generator voltage with its voltage and frequency values are 
within the nominal ranges, generator operation can be switched to using the keys arranged in the mimic dia-
gram. 
 

 

Summary of Contents for KEA 252 PA

Page 1: ...nd displays required in VDE 0108 including the drag indicator display are fulfilled by this automatic system Also the requirements for the control of a diesel motor have been fulfilled in accordance w...

Page 2: ...to the preceding model KEA 102 PA 5 7 Automatic operation 5 7 1 Back synchronisation 5 7 2 Peak load operation 5 8 Test operation 6 9 Basic operation of automatic system 6 9 1 Operation of the display...

Page 3: ...r 13 13 2 11 Monitoring the flows 13 13 2 12 Synchronisation fault 14 13 2 13 Power controller defective 14 13 2 14 Cos controller defective 14 13 2 15 Reverse power 14 13 2 16 Maintenance interval re...

Page 4: ...the unit The connection regulations must be observed 2 The PE N must be connected to the terminal 5 of X403 3 The shields of the analogue signals must only be connected to the earthing screw next to...

Page 5: ...os or other controllers 21 Parameterisation via LWL or USB interface automatic switching or direct via the keys and the display 22 Two CAN bus interfaces 23 Diverse expansion options Modem pressure co...

Page 6: ...hrough forwards and backwards using the and cursor keys Within a group they are read like lines of a text from top to bottom The lines are selected by pressing the cursor buttons down and up If the en...

Page 7: ...isation is described in the service manual The parameters of this group can be changed without a valid ID number Switch on time of the display lighting After pressing any button the background lightin...

Page 8: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 9: ...for monitoring All functions U U f f and the response values of the voltage monitors can be parametrised The un dervoltage display also appears if the measuring voltage is connected with a left rotat...

Page 10: ...tching to OFF from another operating mode a genset operation is immediately ended Previously displayed alarms except fault messages 13 and 14 are deleted as long as the respective alarm contact is sti...

Page 11: ...dynamically determined as a master and ensures the load distribution A deselected relieved genset except for the last one switches off and shuts down after the run on time 12 4 3 Peak load with mains...

Page 12: ...f a switch off alarm occurs the collective switch off alarm is output 13 Alarm messages For contact inputs the respective alarm is triggered with the closing operating current circuit or with the open...

Page 13: ...rect monitoring output a relay can be parameterised at standby current such that the message is passed on with standby current even when in OFF operating mode 13 2 7 Analogue input alarms The analogue...

Page 14: ...rised time the actual value must have been within the dead zone this alarm is issued Optionally the genset can be shut down or a peak load start command can be cancelled for example 13 2 14 Cos contro...

Page 15: ...2 Hz GEN Display of the generator voltage against the neutral conductor in the order L1 L2 and L3 and the generator frequency 6 403 400 398 V L1 2 L2 3 L3 1 G Display of the phase to phase voltages fr...

Page 16: ...indicator synchroscope Display 18 runtime until the next maintenance The operating hours counter until the next maintenance is decremented from a maximum value If the counter reading reaches 000000 an...

Page 17: ...tpoint adjuster or directly to the generator via an analogue signal After suspension of parallel operation the generator voltage is controlled in the parametrised window for the voltage control in sta...

Page 18: ...ogue input 0 20 mA channel 4 for variable power specification in mains parallel operation Battery voltage monitor Input for pick up Three free analogue inputs can be optionally equipped with sub board...

Page 19: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 20: ...___________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen Luh...

Page 21: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 22: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 23: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 24: ..._________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Page 25: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Reviews: