background image

   Operating instructions for KEA 252 PA             

16 / 25

       File: BA_KEA 252 PA_EN_Ver 2016-07-01 

 

______________________________________________________________________________________ 

Alfred Kuhse GmbH 

Telephone: +49 4171-798-0 

kuhse@kuhse.de 

Subject to technical changes 

An der Kleinbahn 39, D-21423 Winsen (Luhe) 

Fax: +49 4171-798-117 

www.kuhse.de 

 

 

18 

RUNTIME  
+  230 h  

 

Runtime until the next maintenance.  

 

 

 

 

19 

DAILY RUNTIME 
010:25 h:m 

 

Resettable short time counter. The counter can be reset to 00:00 here.  

 

20 

 5.6 BAR 
   OIL PRESSURE 

  Example of the analogue channel 1 display. The text can be entered with 

ParaWin. 

 

 

   

21 

98 DEGREES   
WATER TEMPERATURE 

  Example of the analogue channel 2 display. The text can be entered with 

ParaWin. 

 

 

   

22 

   CHANNEL 3 
   NOT USED

 

  Example of the analogue channel 3 display. The text can be entered with 

ParaWin. 

 

 

23 

+  300 kW   GEN. 
PWR REF. VALUE

 

  Example of the analogue channel 4 display. Here the external reference 

value specification for peak load operation. The text can be entered with 
ParaWin. 

 

 

   

24 

+ 3400 mV 
 SPEED CONTROLLER

 

  The example of the display of analogue output channel 5. Here the signal 

to the speed controller. The text can be entered with ParaWin. 

 

25 

+ 1205 mV 
COS PHI CONTROLLER

 

  In the example of the display of analogue output channel 6. Here the signal 

to the cos φ controller. The text can be entered with ParaWin. 

 

 

Display 13, synchroscope 
If the synchronisation is not selected, the synchroscope lettering appears instead of the symbols. If the system to be con-
nected is too fast, the indicator runs in a clockwise direction; if it is too slow, it runs anti-clockwise. This display is analogue 
to the display of an indicator synchroscope. 

Display 18, runtime until the next maintenance 
The operating hours counter until the next maintenance is decremented from a maximum value. If the counter reading 
reaches 000000, an alarm is triggered (if parametrised). A grace period during which the maintenance must be carried out 
can be parametrised. The runtime counter until the maintenance now shows negative operating hours. If no maintenance 
has been carried out even after the grace period has expired, another alarm can be activated.  
If the grace period is set to 000000, the counter does run into the negative range. It can be set on the display. Thus, the 
Maintenance interval reached alarm is deleted. 
If a grace period of > 0 is entered (e.g. during the guarantee period), the counter can only be set by the supplier and only 
with ParaWin. Therefore, the Maintenance interval and Maintenance interval exceeded alarms can only be deleted by 
authorised persons. 

Display 19, daily runtime 
Here, the operating hours are counted up to 999 hours and 59 minutes. It is used for recording short runtimes (e.g. during 
trial operations or mains failures). It can be set to 00:00 without the main operating hours counter being changed. 

 

 

15. 

Further functions 

15.1. 

Frequency controller in standalone operation 

The automatic system issues commands for the speed controller if the function is enabled if the frequency is not 
within the parametrised window. A break is taken between two commands in order for the motor to have time to 
carry out the order. 

15.2. 

Voltage controller in standalone operation 

The automatic system issues commands for the generator voltage controller if the function is enabled and if the 
voltage is not within the parametrised window. A break is taken between two commands in order for the genera-
tor voltage control to settle. 

Summary of Contents for KEA 252 PA

Page 1: ...nd displays required in VDE 0108 including the drag indicator display are fulfilled by this automatic system Also the requirements for the control of a diesel motor have been fulfilled in accordance w...

Page 2: ...to the preceding model KEA 102 PA 5 7 Automatic operation 5 7 1 Back synchronisation 5 7 2 Peak load operation 5 8 Test operation 6 9 Basic operation of automatic system 6 9 1 Operation of the display...

Page 3: ...r 13 13 2 11 Monitoring the flows 13 13 2 12 Synchronisation fault 14 13 2 13 Power controller defective 14 13 2 14 Cos controller defective 14 13 2 15 Reverse power 14 13 2 16 Maintenance interval re...

Page 4: ...the unit The connection regulations must be observed 2 The PE N must be connected to the terminal 5 of X403 3 The shields of the analogue signals must only be connected to the earthing screw next to...

Page 5: ...os or other controllers 21 Parameterisation via LWL or USB interface automatic switching or direct via the keys and the display 22 Two CAN bus interfaces 23 Diverse expansion options Modem pressure co...

Page 6: ...hrough forwards and backwards using the and cursor keys Within a group they are read like lines of a text from top to bottom The lines are selected by pressing the cursor buttons down and up If the en...

Page 7: ...isation is described in the service manual The parameters of this group can be changed without a valid ID number Switch on time of the display lighting After pressing any button the background lightin...

Page 8: ...reen display after the genset start up signals the release of the operating dependent delayed alarms As soon as the motor has started up this display flashes until the monitoring is enabled The displa...

Page 9: ...for monitoring All functions U U f f and the response values of the voltage monitors can be parametrised The un dervoltage display also appears if the measuring voltage is connected with a left rotat...

Page 10: ...tching to OFF from another operating mode a genset operation is immediately ended Previously displayed alarms except fault messages 13 and 14 are deleted as long as the respective alarm contact is sti...

Page 11: ...dynamically determined as a master and ensures the load distribution A deselected relieved genset except for the last one switches off and shuts down after the run on time 12 4 3 Peak load with mains...

Page 12: ...f a switch off alarm occurs the collective switch off alarm is output 13 Alarm messages For contact inputs the respective alarm is triggered with the closing operating current circuit or with the open...

Page 13: ...rect monitoring output a relay can be parameterised at standby current such that the message is passed on with standby current even when in OFF operating mode 13 2 7 Analogue input alarms The analogue...

Page 14: ...rised time the actual value must have been within the dead zone this alarm is issued Optionally the genset can be shut down or a peak load start command can be cancelled for example 13 2 14 Cos contro...

Page 15: ...2 Hz GEN Display of the generator voltage against the neutral conductor in the order L1 L2 and L3 and the generator frequency 6 403 400 398 V L1 2 L2 3 L3 1 G Display of the phase to phase voltages fr...

Page 16: ...indicator synchroscope Display 18 runtime until the next maintenance The operating hours counter until the next maintenance is decremented from a maximum value If the counter reading reaches 000000 an...

Page 17: ...tpoint adjuster or directly to the generator via an analogue signal After suspension of parallel operation the generator voltage is controlled in the parametrised window for the voltage control in sta...

Page 18: ...ogue input 0 20 mA channel 4 for variable power specification in mains parallel operation Battery voltage monitor Input for pick up Three free analogue inputs can be optionally equipped with sub board...

Page 19: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 20: ...___________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen Luh...

Page 21: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 22: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Page 23: ...1 docx _________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 214...

Page 24: ..._________________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Page 25: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Reviews: