KEA 320 / KEA 320 RP
BA-KEA 320 / KEA 320 RP_EN Version 03
Date: 16.Sep.2020
Page 16 of 21
The fuel solenoid relay will not be enabled.
The start request is ignored.
The start push buttons (softkeys) are disabled.
The engine/generator monitoring remains activated (exception: all monitoring that is delayed by the
engine speed).
If the operating mode STOP is selected while the engine was running the following applies:
Dependent on the current application mode a soft shut down will be executed.
Pressing the STOP button again opens the GCB.
If the STOP button is pressed again, the cool down will be interrupted.
If the operating mode STOP is selected while the engine performs a cool down the following applies:
Pressing the STOP button again causes an immediate stop of the cool down and stops the engine.
If the conditions of the LogicsManager function "Enable MCB" (parameter
12923 p. 236/ p. 945) are TRUE, the MCB will be closed again if it is open in
STOP operating mode.