User Manual
KEA 320 / KEA 320 RP
BA-KEA 320 / KEA 320 RP_EN Version 03
Date: 16.Sep.2020
Page 17 of 21
4.2.2
Operating Mode MANUAL
General usage
In the MANUAL operating mode (mode button “MAN” illuminated) both the engine circuit breaker and the
power circuit breaker can be operated via the push buttons along the bottom of the display (softkeys).
Additionally the Start(I)/Stop(O) buttons can be used to start or stop the engine.
1
Mode button: MAN
2
START button: Engine
3
STOP button: Engine
4, 6
Soft buttons: Breaker OPEN/CLOSE
5
Soft button not used
Fig. 10:
KEA 3X0 MAN-buttons
Use the mode button “MAN” to activate operating mode MANUAL.
The MAN button is illuminated.
The breakers will open immediately without power reduction. To open the
breaker in a no-load condition, reduce the load manually in the setpoints
screen (Chapter 4.1.5 “Specialized Menu Screens” on page 107)).
Example for application mode A01
To start the engine:
Press the button [I] below the MAN button.
Success: The engine starts and the circular arrow and the eye symbol appear.
Failure: No change in the display until the "start failure" message appears.
To stop the engine:
Press the button [0] right below the MAN button.
Success: The engine stops and the circular arrow and the eye symbol disappear.
Failure: No change in the display until the "stop failure" message appears.