Figure 21: Wiring diagram for PK2 system package
3.2
PK3 system package - pellet boiler with combi-buffer tank
The system proposal in accordance with the PK3 system package permits the construction of a straight-
forward, economical and space-saving pellet heating system with a combi-buffer tank and an unregulated
domestic water heater. A 4-way mixing valve is not sufficient to serve as a return flow booster for this
system. For this reason the Thermomix valve must be fitted. In particular, this system design is also suit-
able for the construction of a solar heating system that is intended to supplement a conventional heating
system.
Ensure that the boiler circulation pump (15) and the heating pump (18) are correctly matched to one
another.
We recommend installing the Thermomix valve and the buffer tank so that they can be completely iso-
lated in order to simplify maintenance work.
Please read the operating and installation manuals for all of the units before installing the system. The
electrical installation for the system may only performed by a qualified electrician. The use of PVC-
insulated cables is not permitted in the boiler.
When installing the combi-buffer tank, remember to check the state of the protective anode in the storage
heater; a defective anode can unnecessarily reduce the service lifetime of the boiler. We recommend
checking the anode at least once a year.
Hydraulic diagram
20
Summary of Contents for PK 10
Page 1: ...Installation manual pellet boiler PK 10 PK 15 and PK 20 May 4 2009 ...
Page 25: ...4 Technical data Figure 26 The PK pellet boiler Figure 27 Connecting dimensions 25 ...
Page 28: ...Figure 29 Wiring diagram for pellet boiler 28 ...
Page 29: ...Figure 30 Wiring diagram for PK 230V conveyor screw drive 29 ...
Page 30: ...Figure 31 Wiring diagram for PK 400V conveyor screw drive 30 ...
Page 31: ...Personal notes 31 ...
Page 32: ... ...