- 10 -
NON-CONTACT EF-DETECTION
Typical Voltage
89V (tolerance : 12V ~ 165V)
177V (tolerance : 81V ~ 272V)
589V (tolerance : 178V ~ 1000V)
Bar-Graph
Indication
-
- - -
- - - - -
Indication :
Bar-graph segments & audible beep
tones proportional to the field strength
Detection Frequency :
50/60Hz
Detection Antenna :
Top side of the stationary jaw
Probe-Contact EF-Detection: For more precise
indication of live wires, such as distinguishing
between live and ground connections, use the
Red (+) test probe for direct contact measurement.
CAPACITANCE
60.00 nF
±(2.0%rdg + 5dgts)
600.0 nF
6.000
F
60.00
F
2)
±(3.5%rdg + 5dgts)
Resolution
Range
2)
±(4.0%rdg + 5dgts)
1)
Accuracy
600.0
F
2000
F
1)
Accuracies with film capacitor or better
2)
Temperature Coefficient : 0.25 x (specified accuracy) / °C
@ (0°C ~ 18°C or 28°C ~ 40°C)
10 pF
100 pF
1 nF
10 nF
100 nF
1
F
VFD_ ACV (with Low Pass Filter)
6.000 V
±(4%rdg + 80dgts)
60.00 V
600.0 V
1000 V
1)
Accuracy
Resolution
Range
10Hz ~ 20Hz
20Hz ~ 200Hz
2)
200Hz~420Hz
±(2%rdg + 60dgts)
6.000 V
60.00 V
600.0 V
1000 V
±(7%rdg + 80dgts)
6.000 V
60.00 V
600.0 V
1000 V
1)
Not specified for fundamental frequency > 400Hz
3)
Accuracy linearly decreases from 2% + 60d @ 200Hz to
7% + 80d @ 400Hz
1 mV
10 mV
100 mV
1 V
1 mV
10 mV
100 mV
1 V
1 mV
10 mV
100 mV
1 V
CREST-MAX CAPTURE MODE
Accuracy :
Specified accuracy plus 250 digits for changes
> 5ms in duration
- 09 -