EA06
SECTION 1 : SUMMARY
EA06 is equipped with 3 separate sensing inputs (1-2,
3-4, 5-6 terminals R.S.T phase), which can survey from
single up to three phase voltages and check the
average voltage from Y, YY or
wiring accordingly to
the generator requirement or user preference.
The AVR is equipped with adjustable under frequency
protection and over voltage protection to prevent
generator from overloading and over excitation.
The 3 LED each represents (Green) normal operation,
(Red) under frequency and (Yellow) over excitation.
The built in EMS filter helps to prevent possible
interference from the AVR to the generator.
SECTION 2 : SPECIFICATION
Sensing Input (1-2, 3-4, 5-6)
EMI Suppression
Voltage
100
290 Vac / 270
520 Vac
Internal electromagnetic interference filtering
1 or 3 phase, selectable by wiring
Frequency
50/60 Hz
Static Power Dissipation
Max.5 watts
Power Input (+, 2)
Voltage
50
280 Vac
Over Excitation Protection
Frequency
50/60 Hz
25
55 Vdc @ 0.1
20 sec
Excitation Output (+ ,
–)
Under-Frequency Knee Point Thermal Drift
Voltage
Max. 63 Vdc @power input 220 Vac
Adjustable range 42
62 Hz
Current
Continuous 6A
Intermittent 7A for 10 secs.
Voltage Thermal Drift
Resistance
10
100 ohms
Less than 3% at temperature range -40 to
+70 ˚C
Fuse Spec.
Slow blow 5 x 20mm S505-6.3A / 250V
Environment
External Voltage Adjustment
Operating Temperature
-40 to +60
˚C
Max. +/- 5% @ 100K ohms 1/2 watt potentiometer
Storage Temperature
-40 to +80
˚C
Relative Humidity
Max. 95%
Voltage Regulation
Vibration
1.5 Gs @ 5
– 30 Hz
Less than +/- 1% ( with 4% engine governing )
5.0 Gs @ 30
– 500 Hz
Build Up Voltage
Dimensions
5 Vac 25 Hz residual volts at power input terminal
150.0 (L) x 115.0 (W) x 41.0 (H) mm
Soft Start Ramp Time
Weight
4 s/- 10%
440 g +/- 2%
ATTENTION
1. AVR can be mounted directly on the engine, genset,
switchgear, control panel, or any position that will not
affects operation. For dimension reference, please see
Figure 1.
2. All voltage readings are to be taken with an
average-reading voltmeter Meggers and high-potential
test equipment must not be used. Use of such
equipment could damage the AVR.
3. Secure all wiring connection. Do not install AVR at a
place with high vibrations to prevent loose connections.
For safety do not touch the heat sink while in operation.
4. Improper setting of under-frequency protection could
cause the output voltage of the unit to drop or become
unstable under with changes in load. Avoid making any
changes to the U/F setting unless necessary.
41.0
20.5
87.0
115.0
122.0
150.0
4
3
2
1
0
B
+
6
5
EA06
5.3
Figure 1
Outline Drawing