___________________________________________________________________________________________ 

EA06

 

SECTION 3 : WIRING / ADJUSTMENTS

 

3.1 

Field Excitation Wiring 

+, 

 

3.1.1  Connect AVR terminal 

+

  to field 

+

, connect 

AVR terminal

  to the field

 

NOTE 

The  Exciter  field  resistance  is  between  10 

  100 

ohm. 

 
3.1.2  If  field  resistance  is  less  than  10  ohm  when 

generator is under full load and the field voltage 
is  under  the  maximum  output,  please  series  a 
suitable  wattage (W) resistor to have the  overall 
field resistance to equal to 10 

 100 ohm. 

 

3.2 

Sensing / Power Input

1-2, 3-4, 5-6

 

3.2.1  Total  of  3  sets  of  independent  sensing  inputs, 

each input voltage equals to 120 / 240V (Center), 
can  be  series  into  Y  or 

  to  connect  to  the 

generator output (3 Phases) for example R-T, T-S, 
S-R,  or  joint  connected  into  a  single  phase 
sensing (See Figure 2 to 13). 

 
3.2.2  Terminal  +,  2  is  the  AVR  power  input,  voltage 

range from 50 

 280V. 

 

3.3 

Frequency Selection (60 Hz) 

When the 2 terminals marked as 60 Hz on the AVR is 
bridged, the system frequency is 60 Hz. In the contrary, 
when  bridge  is  removed  the  system  frequency  is  50 
Hz. 
 

3.4 

External Voltage Adjustment VR 

Connect  a  100K  Ohms  1/2W  voltage  rheostat  at  VR 
terminals  to  enable  a  +/-  5%  voltage  adjustment  from 
rated voltage. 
 
*

 

The  terminals  must  be  bridged  when  the  external 
voltage adjustment function is none required. 

 

3.5 

Terminals B, 0 can remain not connected 

 
3.6 

VOLT. Voltage Adjustment 

User  can  adjust  the  generator  voltage  by  rotating  the 

VOLT

potentiometer  on  the  AVR.  Rotate  the 

potentiometer  clockwise  to  increase  voltage  and 
decreasing when rotate counterclockwise. The voltage 
adjust  rate  is  less  than  1%  when  the  power  factor 
equals to 1 to 0.8 (PF 1 to 0.8) and frequency variation 
within 6%. 
 

3.7 

STAB. Stability Adjustment 

3.7.1  Slowly  and  precise  adjustment  of 

STAB

potentiometer  can  change  the  respond  time 
between  the  AVR  and  generator.  Inadequate 
adjustment will cause voltage instability and over 
adjusting  will  cause  sudden  overly  voltage 
variation under heavy load. 

3.7.2  Analogue type multi voltmeter is suggested when 

adjusting  the  voltage  stability.  Adjust  the 

STAB

  potentiometer until the pointer on the 

multi voltmeter is oscillating to its minimal. 

 

3.8 

Circuit Protection 

3.8.1  AMP.  Over  Excitation  Protection  Adjustment 

(Overload protection) 

 
 

Set the 

AMP

Overload protection value (25 to 

55  Vdc)  according  to  the  generator  maximum 
excitation  voltage.  When  over  excitation  occurs 
wait for 20 seconds then decrease the generator 
voltage  to  30  to  50  Vac.  When  the  Over 
excitation protection is activated the  yellow LED 
will  illuminate,  the  higher  the  over  excitation 
value  is  the  shorter  delay  time  becomes.  The 
generator will require stopping operation to reset. 

 
3.8.2  Hz. Under Frequency Protection Adjustment 
 
 

Hz.

Is  used  to  set  the  under  frequency 

protection  knee  point.  When  the  generator 
frequency declines to setting point, the generator 
voltage  will  also  decrease  in  the  same  time  to 
prevent  high  excitation  current  from  damaging 
the AVR or the exciter, adjustment procedure : 

 

Adjustment procedure : 

(1)  Start generator and let voltage build up. 

(2)  Adjust  engine  frequency  to  the  appropriate 

low frequency value. 

(3)  Slowly  adjust  Hz.  Potentiometer  until  the  red 

LED illuminates. 

 
SECTION 4 : OPERATION PROCEDURE 

4.1 

Please  confirm  the  follow  condition  before 
starting the generator : 

 

4.1.1  Starting Setting 

(1)  Confirm  if  the  AVR  specification  conforms  to 

the system requirements ? 

(2)  Confirm the AVR wiring ? 

(3)  Confirm correct frequency selected ? 

(4)  Confirm  the  generator  rated  voltage  with  the 

AVR sensing input ? 

(5)  Adjust

VOLT

potentiometer 

fully 

counterclockwise? 

 

Adjust

STAB

potentiometer  to  the  center 

position? 

 

Adjust

AMP

potentiometer fully clockwise? 

 

Summary of Contents for EA06

Page 1: ...Dist Kaohsiung City 80664 Taiwan EA06 Generator Automatic Voltage Regulator Operation Manual Suitable for Single or Three Phase Self Excited Brushless Generator Compatible replacement for Mecc Alte UVR6 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ...rmittent 7A for 10 secs Voltage Thermal Drift Resistance 10 100 ohms Less than 3 at temperature range 40 to 70 C Fuse Spec Slow blow 5 x 20mm S505 6 3A 250V Environment External Voltage Adjustment Operating Temperature 40 to 60 C Max 5 100K ohms 1 2 watt potentiometer Storage Temperature 40 to 80 C Relative Humidity Max 95 Voltage Regulation Vibration 1 5 Gs 5 30 Hz Less than 1 with 4 engine gover...

Page 3: ...ent 3 7 1 Slowly and precise adjustment of STAB potentiometer can change the respond time between the AVR and generator Inadequate adjustment will cause voltage instability and over adjusting will cause sudden overly voltage variation under heavy load 3 7 2 Analogue type multi voltmeter is suggested when adjusting the voltage stability Adjust the STAB potentiometer until the pointer on the multi v...

Page 4: ...oint B Severely deformed generator output wave form C Capacitive load over ratio Power factor in lead D Change the AVR and restart E Under over excitation voltage protection Overload protection SECTION 5 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 5 1 The polarity of f...

Page 5: ...5 R 60HZ 1 3 2 0 B N T Field VR S R S T N T N R S winding 3 4 6 5 60HZ 1 0 2 B VR R S T N Auxiliary Field 3 T 4 5 6 N R S 60HZ 0 1 2 B Auxiliary winding VR Field R T S N winding R S T N Auxiliary Field T N R S Auxiliary winding 3 5 4 6 0 1 2 60HZ B VR Field T N R S Figure 5 3 phase 240 277 Vac Figure 6 1 phase 120 240 Vac With auxiliary winding 3 4 6 5 0 1 2 VR 60HZ B R S T N Field T N R S 3 4 6 5...

Page 6: ...3A 3 VR Terminal SR7 1 1 N T S R 5 6 2 4 3 Field Auxiliary B 0 winding 60HZ VR N S T R 4 3 5 6 4 4 S Field S winding Auxiliary T N 0 1 3 4 5 2 6 5C 4 5 B 60HZ VR 3 1 3A SR7 Terminal 5 6 T N 4 5C Auxiliary winding R S N T R 4 6 5 0 2 3 1 5C 4 5 60HZ B VR 1 3 3A Field Terminal SR7 R 5 6 S T R N 4 5C 2 3 5 2 3 5 Figure 14 1 phase 120 240 Vac Figure 15 1 phase 120 240 Vac With auxiliary winding Field ...