___________________________________________________________________________________________
EA200A
7
SECTION 4 : TERMINAL CONNECTION
TB2
A1
A2
C1
C2
S1
S2
VR1
VR2
B+
B-
TB3
TB1
F+
F-
AC2
AC1
4.1 Excitation field output Terminal
TB1
F+
、
F-
Connect Excitation Field + and
−
The recommended wire diameter is 60mm
2
or 00(2/0)AWG or greater
4.2 Power input Terminal
NFB
AC1
、
AC2
Connect Power Input
The recommended wire diameter is 60mm
2
or 00(2/0)AWG or greater
4.3 TB2 Signal Input / Output Terminal
TB2
OVER TEMP.
ALARM
Over Temp. Pre-Alarm Output Contact (Max. 2A @ 250 Vac)
Contact CLOSED when Temp. is over
100˚C
;
Contact OPENED when Temp. is below
90˚C
(Refer to Section 7)
OVER TEMP
SHUTDOWN
Over Temp. Shutdown Contact (Max. 2A @ 250 Vac)
Contact CLOSED when Temp. is over 130˚C
;
Contact OPENED when Temp. is below 120˚C
(Refer to Section 7)
BATTERY
ABNORMAL
Battery Voltage Abnormal Alarm Contact (Max. 2A @ 250 Vac)
Contact CLOSED when Battery voltage is below 20V or over 28V
OIL SW
Oil Pressure Switch for Automatic Flashing Unit (Refer to Section 6)
EMERGENCY
SHUTDOWN
External Emergency Stop Switch to Stop Power Output to Generation
OPEN ː Normal Operation, CLOSE ː STOP Power Output to Generation
(Refer to Section 8)
Figure 4