KUUMIC OY
NETWORK CONTROL
MIMIC BOARD
8
The addresses for the Display Control Modules (DCM) are formed using the
formula:
write address of the DCM =
(bus cable - 1) x 14 + DCM number + 4700
where
-bus cable
is the cable number to which the DCM
is connected
(bus cables are numbered from 1 to 16)
-
DCM number
is defined by the board-number-select-jumper
inside the DCM Control Module (1-14, see Figure 5)
The addresses for the DCM starts from 4701 dec. and continues to 4924 dec.
Examples:
- first DCM address
-bus cable = 1
-DCM number = 1
address = (1-1) * 14 + 1 + 4700
= 4701 dec
- 15th DCM address
- bus cable = 2
- DCM number = 1
address = (2-1) * 14 + 1 + 4700
=4715 dec