Troubleshooting Electrical Problems
1-15
KVAL Operation/Service Manual
1.
Turn the panel disconnect switch in the off position, open the electrical panel door.
2.
Observe the disconnect switches. Look for loose or broken wires at the disconnect
then at all of the components.
3.
Check for continuity of all fuses with an OHM meter. (Fuses need to be removed
from the bottom side of the fuse holder before measuring the fuses)
4.
With the power off, check for motor overloads by pressing each reset button (usu-
ally at the bottom of the panel) in SEQUENCE. If one is tripped there will be a
slight resistance to touch and a “click” sound as it is reset.
Trip Indicator
Press Reset
Thermal Overload Relay
Test
Check for Tripped Circuits
1.
Remove lock and tag outs on the main power sources.
2.
Manually close disconnect sensors and energize the control circuit or transformer
with its respective sensor. Check the Status Light Panel,. If all lights are observed,
there are no overloads or emergency stops tripped.
Note:
Most electrical problems are related to mechanical malfunction (e.g., stuck
motors, jammed chain, blocked photo sensors etc.)
Note:
If a solenoid valve is suspected, and not cleared in the air checks section (see),
it can be electrically jumped to check operation.
Summary of Contents for 777
Page 4: ...KVAL 777 Operation Service Manual ...
Page 23: ...Getting Help from KVAL 1 15 KVAL 777 Operation Service Manual Page Intentionally Left Blank ...
Page 48: ...Description of the Six Light Panel KVAL 777 Operation Service Manual 2 24 ...
Page 92: ...Troubleshooting with the Status Light Panel KVAL Operation Service Manual 1 20 ...
Page 95: ......