Kvaser Memorator Light User’s Guide
17 (23)
Figure 6: Firmware update, screenshot
5.6
Required driver version
Driver (CANLIB) version 4.1 or later is required to use the Kvaser Memorator Light.
5.7
CAN bus termination
Every CAN bus must be terminated with a 120
Ω
resistor at each end of the bus.
The Kvaser Memorator Light does not contain any CAN bus terminators, because
their inclusion could cause severe disturbance in a system which is already
correctly terminated.
For laboratory or testing use, the exact value of the termination resistors is not
always critical. Sometimes a single terminator is sufficient. For production, proper
termination is essential. If you see error frames on the bus, you should check the
termination.
To save yourself a lot of trouble, always terminate the CAN
bus properly
5.8
CAN bus silent mode
The Kvaser Memorator Light is always in silent mode on the CAN bus.
The Kvaser Memorator Light never transmits CAN messages, error frames, or
acknowledgement bits on the bus. Therefore, two other nodes must exist on the
Kvaser AB, Mölndal, Sweden — www.kvaser.com