Diajekt Control CFC10
24
Status: 06/18/2014
1.8.1 Parameter List
Nr
Parameter
Meaning
Values Margin
Standard
Unit
P01
Display language
Display language of user interface
English/German
German
-
P02
Pressure-independent
release period
Period during which a release is
always granted even if the
differential pressure is too low
1
… 150
90
[ s]
P03
Max. duration of
off-limit condition
How long the differential
pressure can be lower than the
setpoint before an error is noted
1
… 30
10
[s]
P04
Min. differential
pressure
Minimum acceptable differential
pressure
3
… 40
8
[Pa]
P05
CF release
Release signal of chimney fan;
No RS, manual start, release, temp., release / temp.
Release
-
P06
Min. CF capacity
Minimum capacity of chimney fan
0
… 100
0
[%]
P07
CF lead time
How long the chimney fan runs at
maximum capacity after start-up
3
… 999
30
[s]
P08
CF overtravel time
How long the chimney fan
keeps running after a heating
phase has ended
1 ... 3600
120
[s]
P09
Temperature limit
Temperature of the fireplace
that causes the chimney fan to
start
-20 ... +500
45
[°C]
P10
Set pressure
Differential pressure that the PID
control tries to maintain
10 ... 50
12
[Pa]
P11
CF error reaction
Behavior of the chimney fan in
case of an error
0%, 100%
0%
-
P12
CF Shutdown
hysteresis
If the set pressure is exceeded by
this value the CF is shut down
completely
5.. 100
10
[Pa]
P13
CF Shutdown delay
The shutdown of the CF is
delayed by this period
1 ... 180
30
[s]
P14
CF Switch-on
hysteresis
If the set pressure is undercut
by this value the CF is switched
on again
0
[Pa]
P15
CF Switch-on delay
Switching the CF back on is
delayed by this period
1..180
5
[ s]
P16
Control P-ratio
Proportional ratio of the chimney
fan control
0.001 ... 10
0.018
-