DDR OT/BACIP Gateway
DDRA 015 v1.1 04/2010
9
Installation Overview C230 ECO-A
1
1
2
2
3
Information
With the cover removed from the boiler control
and the power turned off, follow the proceeding
steps.
1. On the rear wall of the boiler control, locate
lower nylon stand-offs. Remove these two
stand-offs by either pressing out towards the
back of the control or cut with side-cutters.
2. With the two stand-offs removed, enlarge the
holes with 3/16” drill bit to allow for the M5
screws which fasten the DIN rail to the control
housing. WATCH FOR METAL SHAVINGS.
3. With the holes enlarged, insert the M5 screws
through the DIN rail out towards the back of
the control and tighten with supplied M5 lock
nut.
Note:
Remove gateway and power supply from DIN
rail. Release the fastening tabs to allow DIN rail
to be separated from housings. The end sections
do not need to be removed from DIN rail.
Caution
Ensure that boiler control power is turned off
before performing any work inside of control.