background image

 

2

Table 1.  Recommended Tilt Angles for Fixed Systems—Based on 

Winter Performance 

 

 

 

 

 

 

 
7. INSTALLING KC MODULES 

The minimum spacing of 0.6 in. (15 mm) is required between the solar 
module and the mounting surface around the perimeter of the solar 
module. The frame of each module has 0.28”

φ

 diameter (7 mm) mounting 

holes (Refer to Module Mounting Specifications).  These are used to 
secure the modules to the supporting structure. An example of a ground 
mounted structure is shown in Figure 2. The four holes close to the corners 
of the module are most often used for attachment. Refer to the Mounting 
Specification Specifications for the position of these holes. Clearance 
between the module frame and the mounting surface may be required to 
prevent the junction box from touching the surface, and to circulate cooling 
air around the back of the module.

 

 If the modules are to be installed on the 

roof or wall of a building, the standoff method or the rack method is 
recommended. 
 
STAND-OFF METHOD:  The modules are supported parallel to the 
surface of the building wall or roof. Clearance between the module frames 
and surface of the wall or roof is required to prevent wiring damage and to 
allow air to circulate behind the module.  
The recommended stand-off height is 4.5 in. (about 115 mm) If other 
mounting means are employed, this may affect the Listing For Fire Class 
Ratings. 
 
RACK:  The supporting frame is used to mount modules at correct tilt 
angles. The modules are not designed for integral mounting as part of a 
roof or wall. The mounting design may have an impact on the fire 
resistance.  
 

FOOT ANGLE

SUPPORT

LEGS

MOUNTING HOLE

ARRAY FRAME

MODULE

 

Figure 2.  Basic Rack or Standoff Mounting Structure

 

 

8. MODULE WIRING 

As shown in Module Mounting Specifications, all of the KC modules utilize 
the Type G junction box except the KC85T, KC85TS, KC125TM, 
KC130TM modules which utilize the Type M junction box (see J-box 
details). This junction box, located on the back side of the module, is 
weatherproof and is designed to be used with standard wiring or conduit 
connections.  Kyocera recommends that all wiring and electrical 
connections comply with the 2002 National Electrical Code (NEC). A cable 
clamp with a minimum rating of  IP65 must be used  to maintain the 
weatherproof integrity of the junction   box.Bypass  diodes are preinstalled 
at factory  

 
Figure 3.  Standard Wiring Examples 
 

To wire Kyocera modules: 

Determine the nominal system array voltage of your system. Each 
panel is equivalent to a 12 VDC nominal block. Standard array 
voltages 12, 24 and 48 volt are shown as examples in Figure 3. 

B. 

Open the "G" or "M" box cover by loosening the screws in the cover. 

C. 

The wire used to interconnect the solar modules may be single or two 
conductors, from 14 AWG (2.08 mm

2

) up to 10 AWG (5.26 mm

2

gauge stranded copper wire, in a “SUNLIGHT RESISTANT” jacket 
UF cable. This cable is suitable for applications where wiring is 
exposed to the direct rays of the sun. The maximum and minimum 
outer diameters of the cable that may be used with the cable 
connector are 8 mm and 6 mm respectively (Figure 4). 

D.  Using a flat blade screwdriver, remove only the appropriate 

"KNOCK-OUTS" from the sides of the "G" or "M" box. 

E.    Route wires through the knock-outs and clamps refer to installation 

example (see

 

Figure 5). 

F. 

 

Gently hand tighten the terminal screws with cross tip (Phillips head) 

screwdriver. Do not over tighten, as the terminal can be damaged. 

      

   (Recommendation Torque : 6 foot-pounds (1.5 Newton-meters)) 

G. 

 

The output wiring from the final module is generally run to a separate 

array junction box. In commercial system, this wiring from the array 
box to the next component (i.e. fuse box. or charge regulator, etc.) is 
generally run in conduit. The maximum electrical rating of an 
acceptable series fuse is 6

15 amperes.  

H. 

After checking that module wiring is correct, close and secure all the 

 junction boxes. Use a Phillips head screw driver to secure all screws 

on the junction box cover to ensure a waterproof seal. 

 

SITE 

LATITUDE IN 

DEGREES 

FIXED TILT ANGLE 

   0

°

TO 15 

  15

°

TO 25

°

 

  25

°

TO 30

°

 

  30

°

TO 35

°

 

  35

°

TO 40

°

 

  40

°

15

°

 

SAME AS LATITUDE 

LA  5

°

 

LA 10

°

 

LA 15

°

 

LA 20

°

 

Reviews: