Digital Phase Open & Reverse Phase & UnderVoltage Relay (GDR-JD01) User's Manual V1.10
14 / 52
Kyongbo Electronics Co., Ltd.
2.9 Insulation Test
Insulation
Resistance
DC 500V
Electric Circuit to
Ground
10MΩ
IEC60255-5
Between Electric
Circuits
5MΩ
Between Electric
Circuit Connections
Commercial
Frequency
Withstand
Voltage
50/60Hz,
1min
Electric Circuit
Bundle to Ground
2kV
IEC60255-5
Between Electric
Circuits
Between Connection
Circuit Contacts
1kV
Impulse
Withstand
Voltage
1.2/50μs,
3 times each
for
positive/negative
polarity
Electric Circuit
Bundle to Ground
5kV
IEC60255-5
Between
Transformer Circuits
Between Transformer
Control Circuits
Between Control
Circuits
3kV
Between Tranformer
Circuit Contacts
Between Control
Power Circuit
Contacts
【
Table 2.8
】
Insulation
Caution) AUX POWER and 485 Communication Circuits enclose surge protection
circuit inside the relay, so do not test insulation resistance test and withstand
voltage test.