Digital Phase Open & Reverse Phase & UnderVoltage Relay (GDR-JD01) User's Manual V1.10
30 / 52
Kyongbo Electronics Co., Ltd.
- 〉
P O R
S e
t
1
. M O D E
:
D T
*
2
.
A N G L E
:
1 0
º
3
.
D T
-
T I M E
:
1 0
.
0 0
s
Press
Key in POR screen, then it will exit this menu and convert to the upper menu.
Detail categories that can be set in POR are as follows.
Category
Range
Setting Unit
Default
Value
Description
MODE
OFF, DT
-
DT
Set OFF, Definite Time
ANGLE
2 ~ 90°
2°
20°
Phase angle Pickup Value
DT-TIME
0.04 ~ 60.00Sec
0.01Sec
2.0Sec
Set the time of
Definite Time
【
Table 6.2
】
POR Menu
6.2.2.3
Protection
▶
RPR Set Setting
It is a category to set the Reverse Phase element, and selecting(
) 3. RPR Set
category in Protection will display the following screen.
- 〉
R P R
S e
t
1
. M O D E
:
D T
*
2
.
D T
-
T I M E
:
1 0
.
0 0
s
Press
Key in RPR screen, then it will exit this menu and convert to the upper menu.
Detail categories that can be set in RPR are as follows.
Category
Range
Setting Unit
Default
Value
Description
MODE
OFF, DT
-
DT
Set OFF, Definite Time
DT-TIME
0.04 ~ 60.00Sec
0.01Sec
0.5Sec
Set the time of
Definite Time
【
Table 6.3
】
RPR Menu
6.2.3
Self-Diagnosis Screen
This menu displays the result of the self-diagnosis function for each diagnosis