8.11
KEW6305
8
.
4 Survey closure
There are two methods for closing a survey.
(1) Manual operation
Pressing
START/STOP
key on
DEMAND
range for at least 2 sec. stops measurement. This
action also stops the measurement started automatically at a preset date and time.
(2) Automatic operation (specifying the time and date)
Preset the stop time and date on
SET UP
range .
●
To stop measurement manually
* Pressing
START/STOP
key on
DEMAND
range for at least 2 sec. stops the measurement.
When it stops, (in case data is to be saved to CF card) the LED status indicator goes off.
●
To stop measurement automatically at the preset time and date
Set the stop time and date on
SET UP
range. This method is available only when the
measurement is started at the preset time and date. When the preset stop time and date has been
reached, (in case data to be saved to CF card) and LED status indicator goes off. The survey is then
closed.
NOTE
* Turning off the instrument ( by setting the Function switch to OFF position) will stop the survey, however
the measured data may be lost. It is recommended that a survey be stopped manually (
START/STOP
key) or by presetting the stop time and date.
* Manually starting a survey renders a preset stop time and date ineffective. The survey has to be closed
manually in this case.
* If the preset start time and date come after the preset stop time and date, the survey cannot be done.
8
.
5 Resetting the demand value
There are two methods for resetting (deleting) the current demand values on the display screen.
* Press
ESC
key on
DEMAND
range at least 2 sec.
* System reset
NOTE
* If it is desired to retain the integration value, start demand measurement without resetting the demand
values. The items on
DEMAND
range other than the max. demand value and corresponding time and
date, are reset automatically.
* Demand value cannot be reset during a measurement or while the instrument is in stand-by mode.