5.1
KEW6305
Arrow mark: Points
towards load side.
5. Wiring configurations
5.1 Important Preliminary checks
DANGER
● Do not make measurements on a circuit in which the electrical potential exceeds AC600V.
● Connect the Power cord to a socket outlet. Never connect it to the socket outlet of AC240V or
more.
● The Clamp sensor, Voltage test leads and Power cord are to be connected to the instrument
first.
● The Voltage test leads or Clamp sensors should not be connected to the input terminals of the
instrument if not required for measurement.
● The instrument should always be connected on the downstream side of a circuit breaker, which
is safer than the upstream side.
● Do not open
-
circuit the secondary side of a supplementary CT while it is energized because of
the high voltage generated at the secondary s
ide terminals.
● Be careful to avoid short
-
circuiting the power line with the un
-
insulated part of the voltage test
probes during the setting up of the instrument.
Transformer jaw tips are designed in such a way
to avoid short
-
circuiting. If the circuit under test has exposed conductive parts, extra care should
be taken to minimize the possibility of shorting.
●
K
eep your fingers and hands behind the barrier during measurement.
WARNING
● To avoid possible electric shock and short
-
circuit, always turn off the line under test when setting
up the instrument.
● Do not touch the un
-
insulated tip of Voltage test probes. The use of safety insulted gloves is
recommended.
● Clamp sensor direction for correct measurement:
Ensure that the arrow mark on the clamp sensor points towards to
load side.