INSTRUCTION MANUAL

DIGITAL CLAMP METER

KEW SNAP

SERIES

KEW2040    600A AC Only Type
KEW2055 1000A AC/DC Type

1.Features

Designed to meet international safety standards.

IEC61010-1.IEC61010-031:2002 & IEC61010-2-032 

Measurement Category (CAT.) IV 600V

Pollution Degree 2

 Double  molded  main  body  provides  comfortable 

 

single handed grip

Data Hold Function

 LCD  Backlight  function  to  facilitate  working  at 

dimly lit situations. (KEW2055 only)

REL function to indicate measurement variation.

(Current, voltage, Resistance measurement)

 MIN/MAX  function  enables  easy  reading  of  min  & 

max value during measurement.

With Continuity & Diode Check Function

 NCV

Non  Contact  Voltage

Function  for  wiring   

check.

600V input protection.

Sleep function to extend battery life.

With Bar Graph, 6039 counts

2. Safety Warnings

This  instrument  has  been  designed,  manufactured  and 

tested according to IEC 61010: Safety requirements for 

Electronic  Measuring  apparatus,  and  delivered  in 

the  best  condition  after  passed  the  inspection.  This 

instruction  manual  contains  warnings  and  safety 

rules  which  must  be  observed  by  the  user  to  ensure 

safe operation of the instrument and retain it in safe 

condition. 

Therefore,  read  through  these  operating  instructions 

before using the instrument.

WARNING

 Read  through  and  understand  the  instructions 

contained  in  this  manual  before  using  the 

instrument.

 Keep  the  manual  at  hand  to  enable  quick 

reference whenever necessary.

 The instrument is to be used only in its intended 

applications.

 U n d e r s t a n d  a n d  f o l l o w  a l l  t h e  s a f e t y 

instructions contained in the manual.

 It  is  essential  that  the  above  instructions  are 

adhered to. 

 Failure  to  follow  the  above  instructions  may 

cause injury, instrument damage and/or damage 

to equipment under test. 

The symbol   indicated on the instrument means that 

the user must refer to the related parts in the manual 

for safe operation of the instrument. It is essential to 

read  the  instructions  wherever  the    symbol  appears 

in the manual.

   

DANGER is reserved for conditions and actions  
that are likely to cause serious or fatal injury.

   

WARNING is reserved for conditions and actions 
that can cause serious or fatal injury.

   

CAUTION is reserved for conditions and actions 
that can cause injury or instrument damage.

 Marks  listed  in  the  table  below  are  used  on  this 

instrument.

User must refer to the manual.
Instrument with double or reinforced insulation
Indicates  that  this  instrument  can  clamp  on 

bare  conductors  when  measuring  a  voltage 

corresponding  to  the  applicable  measurement 

category, which is marked next to this symbol.
AC

 

DC
AC & DC

DANGER

 Never make measurement on a circuit in which 

voltage over AC600V exists.

 Do  not  attempt  to  make  measurement  in  the 

presence  of  flammable  gasses.  Otherwise,  the 

use  of  the  instrument  may  cause  sparking, 

which can lead to an explosion.

 Transformer jaw tips are designed not to short 

the  circuit  under  test.  If  equipment  under  test 

has  exposed  conductive  parts,  however,  extra 

precaution  should  be  taken  to  minimize  the 

possibility of shorting.

 Never  attempt  to  use  the  instrument  if  its 

surface or your hand is wet.

 Do not exceed the maximum allowable input of 

any measuring range.

 Never  open  the  Battery  cover  during  a 

measurement.

 The instrument is to be used only in its intended 

applications  or  conditions.  Otherwise,  safety 

functions  equipped  with  the  instrument  doesn t 

work, and instrument damage or serious personal 

injury may be caused.

WARNING

  Never  attempt  to  make  measurement  if  any 

abnormal  conditions,  such  as  broken  case 

and  exposed  metal  parts  are  found  on  the 

instrument.

 Do  not  rotate  the  Function  Switch  while  the 

test leads are being connected.

  Do  not  install  substitute  parts  or  make  any 

modification  to  the  instrument.  For  repair  or 

re-calibration,  return  the  instrument  to  your 

local distributor from where it was purchased.

  Do  not  try  to  replace  the  batteries  if  the 

surface of the instrument is wet.

 Disconnect  all  the  cords  and  cables  from  the 

object under test and power off the instrument 

before  opening  the  Battery  Cover  for  Battery 

replacement.

 Verify  proper  operation  on  a  known  source 

before  use  or  taking  action  as  a  result  of  the 

indication of the instrument.

 Use  appropriate  personal  protective  equipment 

such as insulating gloves, Insulating boots, and 

safety glasses.

 

CAUTION

 Set  the  Function  Switch  to  an  appropriate 

position before starting measurement.

 Firmly insert the test leads.

 Disconnect  the  test  leads  from  the  instrument  

for current measurement.

 Do not expose the instrument to the direct sun, 

high temperature and humidity or dewfall.

 Altitude  2000m  or  less.  Appropriate  operating 

temperature is within 0

 and 40

.

 This instrument isn t dust & water proofed. Keep 

away from dust and water.

 Be  sure  to  power  off  the  instrument  after  use. 

When  the  instrument  will  not  be  in  use  for  a 

long period, place it in storage after removing 

the batteries.

 Use  a  cloth  dipped  in  water  or  neutral 

detergent  for  cleaning  the  instrument.  Do  not 

use abrasives or solvents.

Measurement categories

 (Over-voltage categories)

To  ensure  safe  operation  of  measuring  instruments, 
IEC61010  establishes  safety  standards  for  various 
electrical  environments,  categorized  as  CAT.I  to 
CAT.IV,  and  called  measurement  categories.  Higher-
numbered  categories  correspond  to  electrical 
environments  with  greater  momentary  energy, 
so  a  measuring  instrument  designed  for  CAT.III 
environments  can  endure  greater  momentary  energy 
than one designed for CAT.II.

CAT.Ⅰ

:  Secondary electrical circuits connected to an 

AC electrical outlet through a transformer or 
similar device.

CAT.Ⅱ

:  Primary  electrical  circuits  of  equipment 

connected  to  an  AC  electrical  outlet  by  a 
power cord.

CAT.Ⅲ

:  Primary  electrical  circuits  of  the  equipment 

connected  directly  to  the  distribution  panel, 
and  feeders  from  the  distribution  panel  to 
outlets.

CAT.Ⅳ

:  The  circuit  from  the  service  drop  to  the 

service  entrance,  and  to  the  power  meter 
and  primary  over  current  protection  device 
(distribution panel).

3. Specification

3-1. Measuring range & accuracy

(accuracy guaranteed at 23

℃±

5

 .humidity 45

85%)

AC Current 600A, 1000A Function

Function

Measuring

Range

Accuracy

KEW2040

KEW2055

600A

0-600.0A

±

1.5%rdg

±

5dgt

(50/60Hz)

±

3.5%rdg

±

8dgt

(40-400Hz)

±

1.5%rdg

±

5dgt

(50/60Hz)

±

3.5%rdg

±

8dgt

(40-400Hz)

1000A

0-1000A

N/A

DC Current 600A, 1000A Function

Function

Measuring

Range

Accuracy

KEW2040

KEW2055

600A

0-600.0A

N/A

±

1.5%rdg

±

5dgt

1000A

0-1000A

N/A

AC Voltage Function

    

Auto-ranging, Input impedance: approx. 10M

Ω)

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

6/60/600V 1-600.0V

±

1.3%rdg

±

4dgt (50/60Hz)

±

3.0%rdg

±

5dgt (40

400Hz)

DC Voltage Function
    

Auto-ranging, Input impedance: approx. 10M

Ω)

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

600mV/6/

60/600V

0-600.0V

±

1.0%rdg

±

3dgt

Resistance

Continuity/Diode Check

Function

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

600

Ω

/6k/

60k/600k

Ω

6M

Ω

0-6M

Ω

±

1.0%rdg

±

5dgt

60M

Ω

6.00M- 

60.00M

Ω

±

5%rdg

±

8dgt

Cont Buzzer 0-600.0

Ω

Threshold value : 60

Ω±

30

Ω

 

Diode

Test voltage: 0-2V

Frequency/  DUTY  Function

Auto-ranging  for 

Frequency

Range

Measuring

Range

Accuracy

KEW2040

KEW2055

ACA

40Hz

400Hz

±

0.5%rdg

±

5dgt

ACV

1Hz

10kHz

0.1-99.9%

(Pulse width/Pulse period)

±

2.5%rdg

±

5dgt

Note: Measurable inputs are: 40Vrms@ACV or 
60Arms@AC600A, 350A@AC1000A Range

3-2. General Specification

Mode of operation 

 :

Δ

∑ mode

Display   

 : max. 6039 counts 

  

     

 (Frequency: 9999) & Bar graph

 Over-range  indication  : "OL"  displayed  when  exceeding 
the  measuring  range.  (except  for  AC/DCV  and  1000A   
                             Function)

Range switching      : 

Auto-ranging / Voltage, Resistance Range

Single range / Continuity, Diode check and DUTY

Sample rate 

  

: three times per second

 Functional construction : 

OFF/ACA/ACV/DCV/

Ω

  KEW2040

OFF/ACA/DCA/ACV/DCV/

Ω

  KEW2055

 Keys 

 

       : 

SELECT(AC/DC switching & /

Ω

/ /

), REL

Δ

,

Hz/DUTY, MIN/MAX, HOLD/ Back Light (KEW2055)

 Power source 

       : DC3V/ R03(UM-4) x 2pcs 

 Low battery warning    : "

" mark is displayed at 

 

 

   

2.4V

±

0.15V or less.

 Temperature  &  humidity  :  23

℃±

5

,  relative  humidity

 

accuracy guaranteed  85% or less (no condensation)

 Operating temperature  :0

40

, relative humidity 

& humidity range       85% or less (no condensation)

Storage temperature      : -20

60

, relative humidity 

& humidity range       85% or less (no condensation) 

Current consumption     : approx. 12 mA 

Sleep Function : Automatically powered off in about 

15 min after the last Function switch operation. 

 Press  any  key  or  rotate  the  Function  Switch  from  
OFF to any  position to exit from the Sleep state.

Applicable Standards 

IEC 61010-1:2001

Measurement CAT. IV  600V  Pollution degree 2

IEC 61010-031:2002, IEC 61010-2-032

   EMC

EN 61326

 ・

EN 55022

 ・

EN 61000-4-2 (performance criterion B)

 ・

EN 61000-4-3 (performance criterion B)

Overload Protection

Current Range 

 : 720A AC/ 10 sec @KEW2040

 

                   1200A AC/DC/ 10 sec @KEW2055

Voltage Range 

 : 720V AC/DC/ 10sec

Resistance Range   : 600V AC/DC/ 10sec

Withstand Voltage

6880V AC 

TRMS 50/60Hz

/ 5 sec

(between Jaws and electrical circuit/ between internal 

circuit and enclosure)

Insulation Resistance    : 10M

Ω

 or more/ 1000V 

 (

between electrical circuit and enclosure

Conductor size

KEW2040: approx. 33mm

KEW2055: approx. 40mm

Dimension

approx. 254(L)

×

82(W)

×

36(D)mm / KEW2055

approx. 243(L)

×

77(W)

×

36(D)mm / KEW2040

Weight : approx.: 300g @ KEW2040

                     : 310g @ KEW2055

Accessories

Test Leads 

Model 7066 / 1 set

Battery               R03

UM-4

/ 2pcs

Instruction manual English, Japanese / 1pce

Carriyng Case      Model 9094/ 1pcs

3-3. Function Keys

The  "

"  mark shows available function at each Range.

DC Current Measurement (KEW2055 only)

HOLD SELECT ZERO

Hz/

DUTY

MAX/

MIN

ACA

ACV

-

DCA

-

DCV

-

-

Ω

-

-

-

-

-

-

-

-

-

4. Preparation for measurement 

4-1. Checking Battery Voltage

Set  the  Function  Switch  to  any  position  other  than  

"

OFF

" . When the display is clear without   "

BATT

"   mark, 

showing,  battery  voltage  is  enough.  When  the  display 

is  blank  or

  "

BATT

"    mark  is  indicated,  replace  the 

batteries according to Section 7, Battery Replacement.

CAUTION

The  Sleep  feature  automatically  powers  the 

instrument  off  in  about  15  min  after  the  last 

switch  or  key  operation.  Therefore,  the  display 

may  be  blank  even  with  the  Function  Switch  set 

to  a  position  other  than    "

OFF

" .  To  operate  the 

instrument  in  this  case,  turn  the  switch  back  to 

the    "

OFF

"    position,  then  to  any  other  position, 

or press any key. Replace the batteries if nothing 

was displayed after above operations.

4-2. Checking Switch Setting & Operation

Confirm  the  Function  Switch  is  set  to  the  correct 

position,  the  instrument  is  set  to  the  correct 

measurement mode, 

and  the  Data  hold  function  is  disabled.  Otherwise, 

desired measurement cannot be made. 

5. Measurement

5-1. AC Current Measurement

DANGER

  Never  make  measurement  on  a  circuit  in  which 

voltage  over  AC600V  exists  to  avoid  getting 

electrical shock.

 Transformer  jaw  tips  are  designed  not  to  short 

the  circuit  under  test.  If  equipment  under  test 

has  exposed  conductive  parts,  however,  extra 

precaution  should  be  taken  to  minimize  the 

possibility of shorting.

  Do  not  make  measurement  with  the  Battery 

Cover removed.

 Disconnect the test leads from the instrument for 

current measurement.

(1)  Set  the  Function  Switch  to  "

600A

"  or  "

1000A

position. (on KEW2040, only  "600A"  is available) 

     AC has been selected by default; press the SELECT 

key,  when  DC  has  been  selected,  to  change  it  to 

AC. AC mark is displayed at the upper left on the 

display. (KEW2055 only)

(2)  Press  the  trigger  to  open  the  transformer  jaws 

and clamp them onto the one conductor under test, 

then  take  the  reading  on  the  display.  Pressing  the 

"

Hz/DUTY

" Key switches the indication in following 

sequence.

AC Current

 

 

 

 Hz

 

 

 

 DUTY

Hz/DUTY

  Function  requires  60A  or  more  at  AC600A 

Range and 350A or more at AC1000A range.

CAUTION

 Max conductor size for KEW2040 is approx dia. 

33mm  and  for  KEW2055  is  approx  dia.  40mm. 

During  current  measurement,  keep  the  trans 

former  jaws  fully  closed.  Other  wise,  accurate 

measurements cannot be taken.

5-2. DC Current Measurement (KEW2055 only)

DANGER

 Never make measurement on a circuit in which 

voltage  over  DC600V  exists  to  avoid  getting 

electrical shock.

 Do  not  make  measurement  with  the  Battery 

Cover removed.

(1)  Set  the  Function  Switch  to  "

600A

"  or  "

1000A

position.  AC  has  been  selected  by  default;  press 

the  SELECT    key,  when  AC  has  been  selected,  to 

change it to DC. 

     DC  mark  is  displayed  at  the  upper  left  on  the 

Transformer 