REPAIR
Damaged Drain Fitting
The following procedure is for the field repair of a broken drain fitting.
Drain Fitting
1. Use a drill with a 1 7/8" (48 mm) hole saw to drill out the bottom of the drain fitting. Be
sure to drill completely through fitting and bottom liner.
2. Apply Teflon tape to threaded end of adapter and screw into threaded end of tee.
3. Apply an ABS and PVC compatible primer and sealer to adapter and inside of drain. Insert
adapter into drain fitting.
Coil/Evaporator
Leaking
The following procedure is for the field repair of the coil/evaporator. The coil/evaporator is
shipped to the end user under pressure. If pressure is not present, perform the following:
1. Isolate the case in the line up that has been identified with a leaking coil/evaporator.
72
Summary of Contents for 6RLG3
Page 3: ...2 6 2006 2 Addendum Ballast Relocation 2 ...
Page 5: ...2 6 2006 4 Addendum Ballast Relocation Wiring Diagram Both Canopy and Raceway 4 ...
Page 6: ...2 6 2006 5 Addendum Ballast Relocation Wiring Diagram for Canopy Light 5 ...
Page 9: ...Plan Views and Cross Sections D6L D6 D6H 8 ...
Page 10: ...D6RL D6R 9 ...
Page 11: ...QD6 10 ...
Page 34: ...D6 Electrical Model Table QD6 1 3 04 Through D6H 1 3 6 UNIT INSTALLATION 33 ...
Page 35: ...D6 Electrical Model Table D6H 1 3 6 Through D6R 1 3 4 UNIT INSTALLATION 34 ...
Page 36: ...D6 Electrical Model Table D6R 1 3 4 Through D6RL G 1 6 UNIT INSTALLATION 35 ...
Page 39: ...Wiring Diagram UNIT INSTALLATION 38 ...
Page 40: ...Wiring Diagram Canopy One 1 and Two 2 Light Rows UNIT INSTALLATION 39 ...
Page 41: ...Wiring Diagram Canopy Two 2 and Three 3 Light Rows UNIT INSTALLATION 40 ...
Page 42: ...Wiring Diagram Canopy Two 2 Light Rows and Nose Light UNIT INSTALLATION 41 ...
Page 43: ...Wiring Diagram Off Cycle Defrost UNIT INSTALLATION 42 ...