STRATUS Multi-Deck Display Case
7
The fail safe time may be extended to a maximum of 28 minutes to allow for store condition variations,
refrigeration system variations, and heavy shopping traffic. If the fail safe time is extended, the termina-
tion temperature must remain at 47°F.
ISSUE DATE: JANUARY 2019
DX6LN-MCU
SINGLE DECK MERCHANDISER
APPLICATIONS
General Case Data
6’
8’
12’
Total Display Area (ft
2
)
28.10
37.40
56.20
Cubic Capacity (ft
3
)
71.60
96.50
143.20
Max Shelf Depth (in) [Top/Bottom]
22/22
22/22
22/22
Weight (lb)
-
-
-
Thermal Load (General)
Evaporator Temperature (˚F)
22
22
22
Discharge Air Temp (˚F)
35
35
35
Discharge Air Velocity (fpm)
200-300
200-300
200-300
Fan Speed (rpm)
2200
2200
2200
Refrigerant Type
R-448A
R-448A
R-448A
Estimated Refrigerant Charge (lbs)
8.00
10.00
14.00
Conventional Thermal Load, Single (Btuh) unlighted
8007
10676
16014
Superheat Setpoint (˚F)
6 - 8
6 - 8
6 - 8
Electrical Data (Amps/Watts)
208V/60HZ/1PH 208V/60HZ/1PH 208V/60HZ/1PH
115V/60HZ/1PH 115V/60HZ/1PH 115V/60HZ/1PH
Evaporator Fan Motor Amps (115 V)
0.60
0.60
0.90
Anti-sweat Heater Amps (115 V)
N / A
N / A
N / A
Lights Amps (115V)
0.43
0.47
0.71
Defrost Heater Amps
N / A
N / A
N / A
Condensate Pump Amps (115 V)
1.90
1.90
1.90
Compressor RLA (208 V)
12.00
15.70
23.20
Condenser Fan Motor Amps (208 V)
2.20
2.20
2.20
Refrigeration Cycle Amps
2.03
2.12
2.69
Defrost Cycle Amps
2.03
2.12
2.69
Evaporation Pan(s) Heater Amps (208 V)
7.21
14.42
14.42
Case Circuit Minimum Circuit Ampacity (Circuit 1)
2.54
2.65
3.36
Case Circuit Maximum Overcurrent Protection (Circuit 1)
15
15
15
Condensing Circuit Unit Minimum Circuit Ampacity (Circuit 2)
17.20
21.83
31.20
Condensing Circuit Unit Max. Overcurrent Protection (Circuit 2)
25
35
50
Evaporation Pan(s) Circuit Minimum Circuit Ampacity (Circuit 3)
9.01
18.03
18.03
Evaporation Pan(s) Circuit Max. Overcurrent Protection (Circuit 3)
15
20
20
1 At ASHRAE conditions. For conditions above 75°F, 55% RH, increase
defrost time by 15 min. Type I refrigerator, intended for use in an area where
the environmental conditions are controlled and maintained that conditions do
not exceed 75°F and 55% relative humidity. Kysor Warren, whose policy is
one of continuous improvement, reserves the right to change at any time
specifications, designs, or prices without incurring obligation. DOE 2017
Compliant
Case Length (ft)
Power Supply (Volts/Hertz/Phase)
Defrosts per Day Failsafe Duration (min)
1
Termination Temp (˚F) Drip Time (min)
6
25
47
0
Defrost Data (IOff Cycle)
Case Data