STRATUS Multi-Deck Display Case
9
Installing Case
1.
Ensure all preparation for installation, as outlined in the above paragraphs, have been fully complied with
and are complete.
2.
If multiple cases are to be installed, find the highest area of the floor to place the first case.
3. All cases must be located on a firmly based floor and be leveled within plus or minus 1/16 inch.
4. Use metal shims where required to support entire length of the cases at each base leg (front and back). All
base legs must be shimmed under the skid rail where the base leg meets the lower rails (typically every 4’
on 4’ and 8’ cases, and every 6’ on 6’ and 12’ cases). If the case is equipped with adjustable leveling legs,
all legs should be adjusted so that all are making equal contact with the floor for equal weight distribution.
WARNING! If any part of the case rail or leveling leg is not supported at each base leg, the case can ap-
pear out of level or become damaged when product weight is added.
5.
If multiple cases are to be installed, refer to the floor plan and install the first case in the lineup by snapping
a chalk line where the front and rear of the cases are to be located.
6.
Continue the chalk line if multiple cases are to be installed. The first case is typically the case that is at the
highest area on the floor.
7.
Connect water drain line. Reference waste outlet (drip pipe) description and location procedure later in this
manual.
8.
Connect input AC power. Reference electrical installation procedure later in this manual.
9.
Connect refrigerant lines. Reference procedure later in this manual.
10. Install all ends, caps, and trim per the applicable instructions contained in this manual.
11. Remove shipping tape on fluorescent lamps and remove all other shipping material.
12. Refer to the operational start up procedures later in this manual. If multiple cases are to be installed, refer
to the following paragraph for installing subsequent cases.
CASE MUST BE LEVELED FROM FRONT TO BACK AND END-TO-END AND SUPPORTED CONTINUOUSLY AS
NEEDED WITH SHIMS UNDER EACH BASE LEG
Shelf standards on back
wall should be aligned
when leveled properly.