After 24 hours of inactivity the pump is energized for 30 sec in order to prevent
the block.
y
After 24 hours of inactivity the 3 way valve is energized for 10 sec in order to
prevent the block.
y
If a request occurs during the anti blocking time, the anti blocking function is
stopped.
y
The function is active also in lockout condition or with the boiler in
“
OFF
”
position.
y
If the temperature detected by the primary temperature sensor falls down under
“
antifreeze thermostat ON
”
the pump is activated and the burner starts keeping
the minimum capacity till the temperature reaches
“
antifreeze thermostat OFF
”
.
y
At this temperature the anti freezing function is disabled and the pump runs for
the
“
CH overrun time.
y
Anti freeze function keeps operating in each working mode (also OFF mode).
y
If the boiler is in lock out condition only the pump is activated.
Anti Blocking Function
Anti Freeze Function