When the boiler takes air from the place
where it is installed, be sure that the opening
ventilation are open.
y
Any malfunction in the ventilation may cause
improper combustion that may lead to Carbon
Monoxide(CO) gas poisoning, a fire, or shorten
product use life.
Please check to make sure that the location has sufficient space to prevent
fire and the walls and ceiling are safe against fire.
y
The unit should be installed near a non-combustible wall(if combustible wall then
install a heat-proof panels).
y
The side of the unit should be at least 150mm away from any inflammables.
y
If right and left walls are non-combustibles then the unit should be at least 45mm
from the walls.
y
Heatproof panels (insulating plate should be at least 3mm of metal or other non-
combustible materials.
y
The top of the exhaust pipe should be at least 150mm from the ceiling.
y
There is a danger of a fire if the above terms are not adhered.
Please install the unit in a boiler room away
from the effects of rain or wind.
y
Any rain or rain may cause improper combustion
causing exhaust fume poisoning.
For B33 Type of installation, Please do not
install the unit above any combusting
appliances or near any air conditioning units.
y
This may cause improper combustion causing CO
poisoning.