These flue systems may be oriented in all the possible directions: front, back, right and left hand.
They may also include some special components, like the concentric bends, in order to reach
some particular position.
If it is necessary to insert some concentric bends, please consider that each of them has a
resistance corresponding to the following linear length:
Then, if it’s necessary, for example, to insert others N
°
2 90
°
bend in the flue system type C53, the
total length that the flue system may reach is not 33,70m but not more than 29,30m
Horizontal/Vertical separate flue system 80/80 mm – Type C53
Calculation of the maximum length with the concentric bend included in the flue system