Installation
Planning the power of the electrical generator
Electrical generator
You must power on the generator before powering on the product.
Verify that the product is turned off before powering on the generator.
LA12X draws 16 A from 230 V.
A typical generator has a power factor of 0.8 and should operate at 70% load for good efciency.
The kVA provision for one LA12X should therefore be:
(16 A x 230 V) / (0.8 x 70 %) = 6.5 kVA
This calculation is an example using typical values. It can be adapted using the table in section
(p.19).
Power cord
The removable power cord is tted at one end with a 32 A powerCON connector.
The other end and the wires color code depends on the cord type, as follows:
type
plug
live
neutral
ground
CE
CN
CEE 7/7, 16 A / 250 V, grounded
GB1002 GB2099, 16 A
brown
blue
green/yellow
US
NEMA L5-30P, 30 A / 125 V, grounded black
white
green
INT
bare ends (local power plug to be tted) black
white
green/yellow
Strictly apply the specic safety regulations of the country of use.
Do not defeat the ground connection of the supplied power cord using an adaptor or any other methods.
A suitable plug must be wired to the INT power cord.
Verify that the plug conforms to the specic voltage and current rating given in section
(p.17).
LA12X user manual (en) version 2.0
18
Summary of Contents for LA12X
Page 1: ...LA12X user manual en...
Page 5: ...Latency 70 Remote control and monitoring 70 Physical data 70 Approvals 71 5...
Page 16: ...Installation Refer to the LA RAK II user manual LA12X user manual en version 2 0 16...
Page 71: ...Approvals Approvals 71 LA12X user manual en version 2 0...
Page 72: ......