-- If a leak is detected, check the components
involved for cleanliness in the thread areas and
proper application of pipe compound before
further tightening.
-- Tighten the gas connection as necessary to
stop the leak.
-- If necessary, replace the parts or components
involved if the leak cannot be stopped.
-- Ensure all gas leaks have been identified and
repaired before proceeding.
9
A authorized gas installation and service agency must
check for proper operating gas pressure upon
installation of the heater.
10.
Light according to instructions on heater or within
owner's manual.
11.
It is extremely important to use the proper size and
type of gas supply line to assure proper functioning of
the heater. Contact your fuel gas supplier or a
qulaified and authorized gas installation agency for
proper line sizing and installation.
12.
Make sure the heater has the proper gas regulator for
the application. A regulator must be connected to the
gas supply so that gas pressure at the inlet to the gas
valve is regulated within the range specified on the
dataplate at all times. Contact your gas supplier, or
the L.B. White Co.,
LLC
if you have any questions.
13.
This heater can be configured for use with either L.P.
gas vapor withdrawal or natural gas. Consult the
heater’s dataplate for the gas configuration of the
heater. Do not use the heater in a propane liquid
withdrawal system or application. If you are in doubt,
contact the L.B. White Co.,
LLC
14.
Eventually, like all electrical/mechanical devices, the
thermostat can fail. Thermostat failure may result in
either an underheating or overheating condition which
may damage critical products and/or cause animal
injury or death. Critical products and/or animals
should be protected by a separate back-up control
system that limits high and low temperatures and also
activates appropriate alarms.
15.
Take time to understand how to operate and maintain
the heater by using this Owner’s Manual. Make sure
you know how to shut off the gas supply to the building
and also to the individual heater. Contact your fuel
gas supplier if you have any questions.
16.
Any defects found in performing any of the service or
maintenance procedures must be eliminated and
defective parts replaced immediately. The heater
must be retested by authorized service personnel
before placing the heater back into use.
8