background image

Recommended Propane Gas Supply

Average Temp º F/ºC

50/10  40/4.4  30/-1.1  20/-6.7  10-12.2  0/-17.8  010/-23

Number of  100 lb. 

TS080

1

1

2

2

2

2

2

/45 KG Cylinders to 

Use Per Heater

TS170

2

2

3

3

3

3

3

*  Cylinders must be manifolded together to allow simultaneous vapor withdrawal from all cylinders.

proper application of pipe compound before

further tightening. 

-- Tighten the gas connections as necessary to

stop the leak.

-- After all connections are checked and any

leaks are stopped, turn on the main burner.

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that

could cause flashback.

-- With the main burner in operation, check all

connections, hose connections, fittings and

joints as well as the gas control valve inlet and

outlet connections with approved gas leak

detectors.

-- If a leak is detected, check the components

involved for cleanliness in the thread areas

and proper application of pipe compound

before further tightening.  

-- Tighten the gas connection as necessary to

stop the leak.

-- If necessary, replace the parts or components

involved if the leak cannot be stopped.

-- Ensure all gas leaks have been identified and

repaired before proceeding.

9. A qualified service agency must check for proper

operating gas pressure upon installation of the

heater.

10. Light according to instructions on heater or within

owner's manual.

11. The heater must have the proper gas regulator for the

application.  Use only the L.B. White regulator

originally supplied with the heater.  This regulator

includes a POL fitting incorporating an excess flow

valve.  The excess flow valve is a safety device which

protects against discharge from the propane gas

supply container if the regulator is broken off.  If the

POL fitting is ever replaced, it needs to be replaced

with an L.B. White POL fitting.  Failure to do so can

result in fires, explosions, loss of property, injury or

death.

12. A regulator must be connected to the gas supply so

that the pressure to the inlet of the gas control valve

is regulated within the range specified on the

dataplate at all times.  Contact your gas supplier or

the L.B.white Co., if you have any questions.

13. This heater is configured for use for propane gas

vapor withdrawal only.  Do not use the heater in an

propane gas liquid withdrawal system or application.

If you are in doubt, contact the L.B. White Co., Inc.

14. The heater must be installed so as not to interfere

with or obstruct normal exits, emergency exits, doors

and walkways.

15. Railing, fencing or suitable substitute materials must

be used to keep the heating equipment from any

people using and visiting the structure.

16. The unit shall be located so that rain, ice, or snow

drainage from the structure does not af fect

equipment operation.  If the unit is mounted outside,

it must be mounted above any pooled or standing

water.  If the unit is to be located on the ground, a

surrounding trench is recommended to drain any rain,

ice or snow away from the unit.

17. The ground and surrounding terrain must be cleared

of any combustible vegetation and other combustible

materials when the heater is mounted outside.

18. Eventually, like all electrical/mechanical devices, the

thermostat can fail.  Thermostat failure may result in

an underheating condition.  The thermostat should be

tested to make sure it turns the heater on and off

within a temperature differential of ±3°F (±1.5 °C).

19. Take time to understand how to operate and maintain

the heater by using this Owner’s Manual.  Make sure

you know how to shut off the gas supply to the

building and also to the individual heater.  Contact

your fuel gas supplier if you have any questions.

20. Any defects found in performing any of the service or

maintenance procedures must be eliminated and

defective parts replaced immediately.  The heater

must be retested by properly qualified service

personnel before placing the heater back into use.

The vaporization of propane is affected by several factors:

the surface area of the container, the liquid level of

propane, temperature surrounding the container, and the

relative humidity.  All of these factors are specific to a site.

Therefore, a degree of experience and judgement is

required to select the proper propane supply.

Although experience is the best guide, the following

recommendations can be used as a starting point.  The

table is based on experience in northern climates where

cold weather and high humidity are prevalent in the winter.

If more or less favorable conditions prevail at a specific site,

adjustments can be made on the basis of experience.

8

PROPANE GAS SUPPLY SIZING

Summary of Contents for Premier TS080

Page 1: ...TTENTION ALL USERS This heater has been tested and evaluated by C S A International in accordance with the requirements of Standard ANSI Z83 7l CSA 2 14 and is listed and approved as a ductable direct...

Page 2: ......

Page 3: ...erty damage personal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns...

Page 4: ...mier 80 30 31 Premier 170 32 33 Warranty Policy 34 Replacement Parts and Service 34 Table of Contents General Information This Owner s Manual includes all options and accessories commonly used on this...

Page 5: ...75 x 34 x 51 30 75x18 25 x 28 25 78 x 46 3 x 71 7 TOP 1 0 3 SIDES 1 0 3 BACK 1 0 3 BLOWER OUTLET GAS Propane Gas U S 6 1 83 Canada 3 05 SUPPLY Natural Gas N A Net Weight lbs kg 81 36 7 153 69 4 Shipp...

Page 6: ...If there is an underground leak the movement of gas through the soil can filter the odorant Propane gas odor may differ in intensity at different levels Since propane gas is heavier than air there may...

Page 7: ...r is equipped with manual reset high limit switches an air proving switch and a redundant gas control valve Never operate the heater with any safety device that has been bypassed Do not operate this h...

Page 8: ...eading of the heated air inside the tent End Diffuser Part Number 26350 DO NOT USE ANY OTHER DUCTWORK DUCTING FIELD FABRICATED DUCTS TARPS STOVE PIPE or any other means of making the connection betwee...

Page 9: ...opane gas vapor withdrawal only Do not use the heater in an propane gas liquid withdrawal system or application If you are in doubt contact the L B White Co Inc 14 The heater must be installed so as n...

Page 10: ...e hanger to cage nuts on back of heater b Mount the hanger using the 1 4 20 x 3 4 in bolts and 1 4 in flat washers Tighten securely See Fig 2 2 Thermostat Storage Bracket Assembly a Align regulator st...

Page 11: ...WITH81 2 LEGS ANDAXLEHOLE 1BOLT5 16 18X1 AND1WASHER5 16 ATEACHEND BOLTS5 16 18X1 QUANTITY10 COTTER PIN See Fig 4 for assembly of components Ensure all hardware is tightened securely WHEEL LEG LIFTING...

Page 12: ...t FIG 8 THERMOSTAT ASSEMBLY RIGIDEND SWIVELEND ADAPTER REGULATORIN BRACKET POWERCORD HEAVYDUTY EXTENSIONCORD WITHGROUND SERIESTAPPLUG THERMOSTAT 1 Connect rigid end of hose to regulator outlet Connect...

Page 13: ...Position duct as shown Eliminate any kinks in duct FIG 9 3 04 m CAGENUTS SLOT WINGSCREW INSERTTABATBOTTOM OFDIFFUSERINTOSLOT BEFORETIGHTENINGWING SCREWSINTOCAGENUTS 1 See Fig 10 for installation of u...

Page 14: ...rotected from damage and water entry Natural Gas Heaters A regulator is required if the supply pressure to the heater is above the maximum pressure stated on the heater s dataplate Connect the natural...

Page 15: ...gnition before air is finally purged from line and ignition takes place FIG 15 When the switch is set to heat four status lights see Fig 15 will be activated in sequence as specific circuits are check...

Page 16: ...ir or a soft brush or dry rag on its case and internal components At this time dust off the motor case to prevent the motor from over heating b At least once a year give the heater a thorough cleaning...

Page 17: ...s defective and must be replaced Do not leave the jumper on or operate the heater if the part is defective Replace the part immediately An alternate method for checking the components is to perform a...

Page 18: ...cracks are found 17 1 2 IN DISTANCE FROM IGNITER TOPTO BURNERTOP MOUNTING BRACKET IGNITER BRACKET MOUNTING SCREWS IGNITER SENSOR MOUNTING SCREWS HIGHVOLTAGE IGNITION LEAD ELECTRODE GAP IS 1 8 CENTERE...

Page 19: ...Holding the switch by one of its mounting legs apply a small flame only to the sensing portion on the back of the switch Be careful not to melt the plastic housing of the switch when conducting this t...

Page 20: ...ded FIG 24 5 When assembling the control valve to manifold the valve must be offset 8 degrees from the orifice holder to ensure the control valve aligns to its mounting holes See Fig 25 FIG 25 8 ORIFI...

Page 21: ...nd outlet pressure gauges agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that speci...

Page 22: ...procedures of the component once the problem is identified by the flow chart DIRECT IGNITION OPERATION SEQUENCE The thermostat calls for heat Light acitvated indicating heater is receiving its main po...

Page 23: ...defective Check continuity Replace power cord Transformer status light is not on Is transformer delivering 24 volts to terminal W on ignition control No Is transformer receiving main voltage Check wi...

Page 24: ...ce fan motor No Yes Are 24 volts received at the air proving switch from terminal PS1 on controller when motor starts Yes Are wires and electrical connections good No Repair or replace wires or connec...

Page 25: ...r end delivering 24 volts to gas control No Is gas control valve receiving 24 volts No Yes Yes Yes Is light receiving 24 volts No Defective wire or terminal connection Repair or replace as needed Yes...

Page 26: ...ntrol is sending high voltage Remove ignition lead from control Hold a screwdriver tip about 1 8 to 3 16 in from male ignition terminal on control Turn heater on Spark should be seen If none replace i...

Page 27: ...proper voltage is not present No No Yes Is proper voltage supplied to selector switch from power cord No Is fan binding on housing Check for damage to fan and housing Repair or replace as necessary Ye...

Page 28: ...K DSI SS T PC HL HL GV APS IGC TX M COMM C W TRANSFORMER PS2 AIRPROVE PS1 AIRPROVE MV VALVE IND MOTOR L1 115 VAC G G G BR BK 115 VAC L1 GY OR OU O BK COMM C TRANSFORMER W AIRPROVE PS1 AIRPROVE PS2 VAL...

Page 29: ...ce that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system which is used to break an electrical circuit...

Page 30: ...29 PREMIER 80 PARTS SCHEMATIC Parts Identification 18 47 13 45 46 44 43 42 41 40 39 38 37 36 35 33 32 31 30 29 27 28 26 25 24 22 23 20 21 19 17 16 15 14 12 11 10 9 7 6 5 4 3 2 1 8 34...

Page 31: ...6378 18 Harness Wire Motor End 26382 19 Base 26380 20 Bracket Igniter Sensor 571663 21 Igniter 571662 22 Burner 26484 23 Screws and Spacers 571211 24 Switch High Limit Burner End 275 F 503933 25 Chamb...

Page 32: ...20 31 PREMIER 170 PART SCHEMATIC 36 17 16 10A 10A 10A 51 49 48 47 46 45 44 43 42 41 39 38 37 35 34 33 32 31 30 29 27 26 25 24 23 21 20 19 15 14 13 12 11 10 9 8 7 5 6 4 3 2 1 50 28 22 18 52 40...

Page 33: ...26441 19 Bracket Ignition Control 26410 20 Ignition Control 25865 21 Orifice Propane Gas 21573 Natural Gas 571624 22 Wire Igniter 25840 23 Igniter 25841 24 Bracket Igniter 25843 25 Burner with Mounti...

Page 34: ...material and workmanship for 24 months from the date of purchase by the end user Warranty is automatic if a component is found defective within 24 months of the date code marked on the part If the de...

Reviews: