3.6.1 Settings Menu
In the Settings Menu, the user can access and change various parameters used by the rectifier section of the
AUPS. To access the Settings Menu, press the
MENU button, select “Settings Menu”
, and press the ENTER
button.
Once in the Settings Menu, the user can navigate the menus with the up and down arrows. To enter a
submenu, use the ENTER button. The BACK button returns to the previous menu. When making a selection, the
ENTER button will store the value and step back. The BACK button will not save the change and will go a step
back. At any point, the settings menu can be exited, with or without saving the settings by continuously
pressing the BACK button.
The settings menu is divided into 4 s
ubmenus: “Float/Eq Voltage”, “Alarm Settings”, “Advanced
Settings”
, and
“Return to Defaults”.
3.6.1.1 Float/Eq Voltage
The Float/Eq Voltage submenu provides access to change the Float Voltage and Equalize Voltage Settings.
Float Voltage Setting
The Float voltage adjustment is set at the factory at 2.17 V/C (LA), 2.25 V/C (VRLA) or 1.4 V/C (NC). The Float
voltage can be adjusted by 0.1V increments.
Select “Float Voltage Setting” and press the
ENTER button. Press
the UP and/or DOWN buttons until the required voltage level is displayed. Press ENTER to store the setting or
BACK to cancel.
The approximate adjustable range is as follows:
2.02
–
2.40 V/C (LA) (VRLA)
1.29
–
1.55 V/C (NC)
Equalize Voltage Setting
The Equalize voltage adjustment is set at the factory at 2.33 V/C (LA), 2.27 V/C (VRLA) or 1.55 V/C (NC). The
Equalize voltage can be adjusted by 0.1V increments.
Select “
Equalize Voltage Settin
g” and press the ENTER
button. Press the UP and/or DOWN buttons until the desired voltage is displayed. Press ENTER to store the
setting or BACK to cancel.
The approximate adjustable range is as follows:
2.15
–
2.50 V/C (LA) (VRLA)
1.40
–
1.70 V/C (NC)
3.6.1.2 Alarm Settings
The Alarm Settings submenu provides access to the change the Alarm Thresholds and Summary Alarm Selects.
Equalize Voltage
139.8V
< Equalize >
Voltage Setting
Float Voltage
130.2V
< Float >
Voltage Setting