21
Alarm Thresholds
The Alarm Thresholds setting allows the user to determine the current or voltage value at which an alarm
triggers. The threshold can be changed for Low Current Alarm, Low Current Alarm Reset, Overload Alarm, Low
Voltage Alarm, Low Voltage Alarm Reset, End of Discharge Alarm, High Voltage Alarm, and High Voltage
Shutdown Alarm.
NOTE:
Alarm threshold defaults are based on the rectifier output. The alarm threshold values shown above are
not representative of the default values for any specific rectifier.
Summary Alarm Selects
The Summary alarm selects setting allows the user to choose whether or not to include the Low Current Alarm
and AC Failure Alarm as part of the Summary Alarm.
NOTE:
The Low DC Voltage and High DC Voltage alarms are included in the Summary alarm and cannot be
removed.
3.6.1.3 Advanced Settings
The Advanced Settings Menu allows the user to access and modify other parameters of the rectifier which are
not included in the basic Settings Menu. The Advanced Settings Menu is divided into 6 submenus: Equalize
Timer Settings, Advanced Alarm Settings, Temperature Compensation, Communication Settings, LCD Settings,
and Return to Defaults.
Equalize Timer Settings
The Equalize Timer Settings submenu provides access to the change the Equalize Timer Mode, and Equalize
Timer Hours.
Equalize Timer Mode
The Equalize timer mode determines when the rectifier will go into an Equalize charging cycle. The timer modes
are Auto EQ OFF, 7 Day Auto EQ, 14 Day Auto EQ, 30 Day Auto EQ, and Auto EQ on LV. The default setting for
the Equalize timer mode is Auto EQ OFF. The Equalize Timer Modes are discussed in further detail in Section
3.5.1.
< EQ Timer Mode
Auto EQ OFF
< Equalize >
Timer Mode
< AC Fail >
Alarm in Summary
< Low Current >
Alarm in Summary
< Summary >
Alarm Selects
< HV Shutdown
Alarm 150.0 V
< High Voltage
Reset 135.0 V
< High Voltage
Alarm 147.0 V
< End Discharge
Reset 10 Percent
< End of
Discharge 100.8V
< Low Voltage
Reset 8 Percent
< Low Voltage
Alarm 118.8 V
< Overload
Reset 16.5 A
< Overload
Alarm 18.0 A
< Low DC Current
Reset 0.4 A
< Low DC Current
Alarm 0.2 A
< Alarm >
Thresholds